DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 3. EntelliGuard TU Trip Unit System
©2012 General Electric All Rights Reserved
Table 3.28. Metering Data Startup Levels for breaker with Entelliguard Trip Unit with 24 VDC
Current
Phase A,B,C,
neutral
A
> 3 % Rating Plug
Current
Voltage Phase L1,L2,L3 V
> 15 V for all Voltage
Ranges
Real Power
Phase L1,L2,L3
and total
kW
> 7% Rating Plug
Current or > 15 Volts
Reactive Power
Phase L1,L2,L3
and total
kVAR
> 7% Rating Plug
Current or > 15 Volts
Apparent Power
Phase L1,L2,L3
and total
kVA
> 7% Rating Plug
Current or > 15 Volts
Peak Demand Power Total
Auto-ranging from
0.00 kWH to 999mWH
> 7% Rating Plug
Current or > 15 Volts
Energy
Phase A,B,C and
total
Auto-ranging from
0.00 kWH to 999mWH
> 7% Rating Plug
Current or > 15 Volts
Frequency Hz
> 10% Rating Plug
Current
Power Factor %
> 7% Rating Plug
Current or > 15 Volts
Note: Metering Data for breaker with Entelliguard Trip Unit without 24 VDC requires 20% sensor current and then all metering will be available
Table 3.29. Accuracy as a Percent of Sensor Rating
Accuracy as a Percent of Sensor Rating
Reading
Figure 3.14 through 3.17 depict selected sensor performance characteristics.