DET-653C  EntelliGuard
®
 G Circuit Breaker Application Guide 
24-May-12  Section 3. EntelliGuard
®
 TU Trip Unit System 
 
  ©2012 General Electric All Rights Reserved 
Table 3.27. EntelliGuard Trip Unit Summary (continued) 
Ground Fault Protection 
External Zero Seq. (Gnd Return) CT 
Input 
0.042/0.058-0.417/0.0917sec 
Zero Selective Interlock 
Separate ZSI Band Settings 
Protective Relays 
10% - 50% difference between highest 
& lowest phase compared to average, 
1% steps; 1 to 15sec delay in 1sec 
110% - 115% of line voltage in 1% 
Steps; 1-15sec delay in 1sec steps 
30% - 85% of line voltage in 1% Steps; 
1-15 Second Delay in 1 sec steps 
10% - 50% difference between highest 
& lowest phase compared to average, 
1% steps;  1 to 15sec delay in 1sec 
Line to Load OR Load to Line, From 10 
to 990kW in 10kW steps 
Current Level (Alarm/Load 
Management) 
Metering, Diagnostic, and 
Miscellaneous Functions 
Waveform Capture (COMTrade) 
Serial Comm. 
Front Port for Local Comm 
I/O 
Flexibility 
Universal Trip Plugs (16) 
Adjustable (20%-100%) Trip Plug 
Universal Spare Trip Unit 
Interchangeable Trip Unit 
All Settings can be performed via the front of the trip unit.   Also available is Free Set-up Software downloadable from 
geindustrial.com   Download and upload trip unit settings. Ability to download and view the waveform captured by the trip 
unit.  Also has the ability to store settings in an Offline file and then compare it to the current settings.   Requires the 
EntelliGuard TU Test Kit, GTUTK20.