DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 5. Catalog Numbering Guide
©2012 General Electric All Rights Reserved
72
Digit 8 Zone Selective Interlocking (ZSI)
Zone Selective Interlocking
Code
ZSI, Short time and GF; user selectable
Z
Z + IOC or HIOC ZSI; user selectable
T
Blank/None
X
ALL ZSI selections require Secondary Disconnect Block B and 24Vdc
control power.
Control power recommended for instantaneous ZSI.
D
Digit 9 Advanced Features and Communications
Advanced Features & Communications
Code
Reduced Energy Let-Through (RELT)
1
Modbus Protocol + RELT
2
Profibus Protocol + RELT
3
Monitoring + RELT, NO Communication
4
Monitoring + Relay Package + RELT
5
Monitoring + Data Acquisition, Modbus
Protocol + RELT
6
Monitoring + Data Acquisition, Profibus
Protocol + RELT
7
Monitoring + Data Acquisition + Relay Package,
Modbus + RELT
8
Monitoring + Data Acquisition + Relay Package,
Profibus + RELT
9
None
X
All Advanced Feature selections require Secondary Disconnect Block B
and 24Vdc control Power.
RELT = Reduced Energy Let Through.
Monitoring = Advanced Metering.
Data Acquisition = Waveform Capture and Harmonic Analysis.
Digit 10 Manual/Auto Trip Reset
Manual Auto Trip Reset
Code
Manual Lockout
M
Auto Reset/Reclose
A
Auto/Manual Lockout (Selectable)
S
None (Defaults to Auto Reset/Reclose)
X
When Bell Alarm with Lockout is selected on the EntelliGuard G Circuit
Breaker, then Code M must be selected.
X is only valid on GE Legacy Circuit Breakers and Conversion Kits.
M is valid on EntelliGuard G Breakers when a Bell Alarm is selected.
A is valid on EntelliGuard G Breakers when a Bell Alarm is not selected.
S is IEC Only
Digit 11 Factory or Field Installed
Manual Auto Trip Reset
Code
Factory Installed Trip Unit (Original)
F
Replacement Trip Unit (shipped loose)
R
EntelliGuard TU Trip Unit Rating Plugs (see page 20)
Sample
GTP
1600
U
16
40
Digit
1,2,3,4
5,6,7,8
9
10,11
12,13
EntelliGuard Trip Unit Rating
Plug
Universal Trip Unit Rating Plug
(Rating in Amperes)
Universal Trip Plug
Smallest Sensor that accepts
this plug (1600A)
Largest Sensor that accepts this
plug (4000A)