DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 4. Accessories
©2012 General Electric All Rights Reserved
Table 4.26. Wiring Schematic for Block-B
(Three Layer Secondary Disconnect to be Added for GTU with Full I/O and Additional Accessory Signals)
INPUT1 INPUT2
I/P
COM
ST1 NO/
NC8
ST1 COM/
NC8
UV1
NO/
UV1
COM/
NC6 NC6 NC5 NC5 NC4 NC4
Max. Voltage (V)
30Vdc/
25Vac
30Vdc/
25Vac
30Vdc/
25Vac
240V/
440V
240V/
440V
240V/
440V
240V/
440V
440V 440V 440V 440V 440V 440V
RELT
INPUT
COM -
CC NO/
NO8
CC COM/
NO8
ST2 NO/
UV2 NO/
NO7
ST2 COM/
UV2
COM/
NO6 NO6 NO5 NO5 NO4 NO4
<50mA <500mA -
10A/
10A/
10A/
10A/15A 15A 15A 15A 15A 15A 15 A
5V 0.1V -
240V
/
240V/
240V/
240V/
440V 440V 440V 440V 440V 440V
ZSI
ZSI
ZSI
ZSI
ISO
5V
TX EN 1 RX TX
GND
Volt-A Volt-B Volt-C
28Vdc 28Vdc 30Vdc 30Vdc 0.1V 5V 5V 5V 5V 0.1V 1.76V 1.76V 1.76V
Table 4.27. Wiring Schematic for Block-C (Internal to the breaker, not used by customer.)
(Two Layer Intermediate Secondary Disconnect at the Top for the Side Mounted Secondary Disconnect.)
BA
NC
BA
NO
BA
COM
ST1
NO
ST1
COM
UV1
NO
UV1
COM
CC
NO
CC
COM
UV2
NO
UV2
COM
NO5 NO5 NO4 NO4 NC3 NC3 NC2 NC2 NC1 NC1
Spr NO/
RTC NO
NO/
RTC
NO
ST1 ST1 UV1 UV1
CC
COM
CC
IMM
CC
CMD
ST2/
UV2
ST2/
UV2
NC5 NC5 NC4 NC4 NO3 NO3 NO2 NO2 NO1 NO1
Table 4.28. Electronic Interlock
Network Interlock Connections
Network Interlock Status Switch
A5 A6 A7 A8 B4 B5 B6
NI TRIP NI TRIP NI RESET NI RESET NI NC NI NO NI COM
1.9A 1.9A 1.9A 1.9A 10A 10A 10A
240V 240V 240V 240V 240V 240V 240V