DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 3. EntelliGuard TU Trip Unit System
©2012 General Electric All Rights Reserved
29
Universal Trip Units may be ordered with a limited set of
options. It is suggested that they be ordered with the widest
range of options used within a facility, as any unnecessary
functions can always be disabled or turned off (except for
Ground Fault) during set up by the user. The user-selected
options for the Universal Trip Unit are listed in Table 3.18.
Table 3.18. Universal Spare Trip Unit Options
(User-Selected)
Feature
#
Option
Long Time
1
Standard (Circuit Breaker Curves)
2
Standard and Fuse Curves
Instantaneous
1
Standard
2
Extended Range
Ground Fault*
1
None
2
Standard (Internal GF)
3
Ground Input
Arc Flash
Protection
1
No RELT
2
RELT
Zone Selective
Interlocking
1
Short Time and Ground Fault
2
Short Time, Ground Fault and
Instantaneous
Communications
1
None
2
Modbus
3
Profibus
Metering
1
Standard (ammeter)
2
Advanced (A, V, E and P)
3
Diagnostic (Advanced and WFC)
* Mains and ties in solidly grounded multiple source substations will usually
require ground input type ground fault protection. Feeders will use standard
internal ground fault protection.
Example Universal Trip Cat#: G1X00L4T6MRXXXX
Description: Universal EntelliGuard TU Trip unit for a
EntelliGuard G Breaker with LSIG, Zone Selective Interlocking
(Short Time, Ground Fault, Instantaneous), Modbus, Full
Metering, Waveform Capture, RELT and Bell Alarm with
Lockout/Manual reset