DET-653C EntelliGuard
®
G Circuit Breaker Application Guide
24-May-12 Section 3. EntelliGuard
®
TU Trip Unit System
©2012 General Electric All Rights Reserved
Table 3.19. Relay Functions Available in EntelliGuard G Circuit Breakers with EntelliGuard TU Trip Units
yes yes yes yes yes
yes yes yes yes yes
yes yes yes yes yes
yes yes yes yes yes
Current Level Alarm, 2 Settings Available
no yes yes yes yes
no yes yes yes yes
3
no no yes yes yes
Ground Fault Alarm Status
no no yes yes yes
Trip Target
no no yes no yes
- - -
Trip Information
no no yes no yes
- - -
Trip Counter
no no yes no yes
- - -
Event Logging (Trips, Alarms, I/O)
no no yes no yes
- - -
Waveform Capture
no no yes no yes
- - -
Current (Phases A, B, C, N)
no no yes no yes
1
no no yes no yes
Real Power (Watts, Per Phase and Total)
no no yes no yes
Apparent Power (Watts, Per Phase and Total)
no
no
yes
no
yes
no
no
yes
no
yes
1 User set to PH-N or PH-PH.
2 Output contacts are low signal (Hi-Fi).
3 When top unit has RELT, output 1 is dedicated to RELT ON status.
The EntelliGuard TU offers various protective and alarm relay
functions that may be displayed on the LCD screen,
assigned contact outputs or communicated serially (Table
3.19).
Protection relays may be set by the user to alarm, trip the
circuit breaker or both. Alarms and trips are displayed on the
local LCD trip and communicated serially. Alarms may also
be assigned to one of two output contacts. The Trip Alarm
settings are independently set for each relay function.
This function compares the highest or lowest phase voltage
with the average of all three phases and initiates a trip if the
difference exceeds the set point. The true RMS voltage is
computed for each phase (Table 3.20).
Table 3.20. Voltage Unbalance Settings
Adjustable from 10% to 50% in
increments of 1%.
unbalance delay
User adjustable from 1sec to 15sec in
increments of 1sec. Setting this value to
zero (0) will disable the relay.