DET-653C  EntelliGuard
®
 G Circuit Breaker Application Guide 
24-May-12  Section 5. Catalog Numbering Guide 
 
©2012 General Electric All Rights Reserved   
 
* P available only as 3-pole. 
 
 
Digit 5- EntelliGuard G Short Circuit and Interrupting Ratings 
Interrupting Rating Tier ANSI/UL1066 Devices, LVPCB 
65,000  65,000  50,000  50,000  50,000  49,000  53,500 
X 
 
65,000  65,000  65,000  65,000  None  None  None 
X  X 
85,000  85,000  65,000  65,000  65,000  63,700  69,500 
X 
100,000  100,000  65,000  65,000  65,000  63,700  69,550 
X         
85,000  85,000  85,000  85,000  None  None  None 
X 
100,000  100,000  100,000  85,000  85,000  83,800  90,950 
X 
100,000  100,000  100,000  100,000  None  None  None 
X 
X 
150,000  150,000  100,000  100,000  100,000  98,000  107,000 
X 
X 
Interrupting Rating Tier UL489 Devices ICCB 
65,000  65,000  50,000  42,000  42,000  N/A  44,940 
X 
65,000  65,000  65,000  42,000  42,000  N/A  44,940 
X  X 
 
85,000  85,000  65,000  50,000  50,000  N/A  53,500 
X  X 
 
100,000  100,000  65,000  50,000  50,000  N/A  53,500 
X         
100,000  100,000  100,000  65,000  65,000  N/A  69,550 
X 
X 
150,000  150,000  100,000  85,000  85,000  N/A  90,950 
X  X 
Close and Latch ratings (MCR set accordingly) 
Notes: Override has 7 % pick up tolerance. Nominal setting is 98% of lcw if 
no other instantaneous is on, or 107% of lcw if any other instantaneous is 
on. UL 489 CB always has other instantaneous protection on. MCR set at 
78% Close and Latch rating with -10% tolerance. -6000A UL 489 CB is 
100% rated as stationary and 80% rated draw-out. 
UL/ANSI 1 
UL/ANSI 2 
UL/ANSI 3 
42,000 
65,000 
100,000 
UL/ANSI CB MCR setting determined based on Envelope only. For 
Retrofill's  (A = 17,000, B = 33,000, N = 42,000) 
42,000  42,000  42,000 
50,000  50,000  65,000  65,000 
100,000 
100,000 
ANSI Non-Automatic Switches 
30 Cycle Withstand Ratings 
Note: Non-automatic switches are provided with 
no internal sensing or tripping mechanism and 
cannot be applied above their respective withstand 
levels. If a non-automatic device is required at 
ratings above the available switches is required, it 
is recommended that a circuit breaker set with 
maximum setting be employed using external 
control or protection as required by the 
application. 
42,000  42,000  42,000 
X 
65,000  65,000  65,000 
X 
100,000  100,000  100,000 
X 
UL489 Non-Automatic Switches 
42,000  42,000  42,000 
X 
65,000  65,000  65,000 
X 
150,000  150,000  100,000 
X