EasyManua.ls Logo

GE Multilin 489

GE Multilin 489
314 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 7: TESTING
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL 7–21
7.3.11 Distance Element Accuracy
The theoretical impedance on the R-X plane can be calculated as:
(EQ 7.10)
where: Z
d
= programmed distance impedance
θ
d
= programmed distance characteristic angle
θ
i
= variable angle on the R-X plane at point i for which boundary
impedance is to be calculated
It is recommended that voltage is kept constant while increasing the current magnitude at
certain angles referenced to voltage phase A until element operates.
Then the expected operating current (assuming that current in the two phases are 180°
apart) can be calculated as:
(EQ 7.11)
where .
Current/voltage (5 A unit) Alarm Trip Trip Delay
Current Voltage
expected observed delay expected observed expected observed
Ian = 5 A0°
Ibn = 5 A120° lag
Icn = 5 A240° lag
Vab = 120 V0° lag
Vbc = 120 V120° lag
Vca = 120 V240° lag
8 N/A 8 N/A N/A
Ian = 6 A0°
Ibn = 6 A120° lag
Icn = 6 A240° lag
Vab = 120 V0°
Vbc = 120 V120° lag
Vca = 120 V240° lag
48N/A N/A
Ian = 10 A0°
Ibn = 10 A120° lag
Icn = 10 A240° lag
Vab = 120 V0°
Vbc = 120 V120° lag
Vca = 120 V240° lag
4411.8 s
Ian = 10 A0°
Ibn = 10 A120°
lag
Icn = 10 A240° lag
Vab = 100 V0°
Vbc = 100 V120° lag
Vca = 100 V240° lag
446.6 s
Ian = 10 A0°
Ibn = 10 A120° lag
Icn = 10 A240° lag
Vab = 60 V0°
Vbc = 60 V120° lag
Vca = 60 V240° lag
441.7 s
4 activated; 8 Not Activated
Z
i
0.875 Z
d
θ
d
θ
i
()cos×× 0.875 Z
d
θ
d
θ
i
()cos××()
2
4 Z
d
2
0.125××++
2
------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------=
I
i
V
a
V
b
2Z
i
-----------------=
Z
i
Z
i
e
jθ
i
×=
Courtesy of NationalSwitchgear.com

Table of Contents

Related product manuals