S4 Elements
745
Transformer Management Relay
Setpoints
http://www.GEindustrial.com/multilin
5–83
GE Multilin
Current Demand PATH: SETPOINTS !" S4 ELEMENTS !" CURRENT DEMAND ! W1(3) CURRENT DEMAND
This section contains the settings to configure the current demand monitoring
elements. Included are a current demand level for each winding and each phase.
FIGURE 5–43: Current Demand Scheme Logic
! CURRENT DEMAND [!] W1 CURRENT DEMAND
FUNCTION: Disabled
Range: Enabled, Disabled
MESSAGE
W1 CURRENT DEMAND
TARGET: Self-Reset
Range: Self-Reset, Latched, None
MESSAGE
W1 CURRENT DEMAND
PICKUP: 100 A
Range: 0 to 65000 in steps of 1 (auto-
ranging)
MESSAGE
W1 CURRENT DEMAND
BLOCK: Disabled
Range: Logc Inpt 1 to 16, Virt Inpt 1 to
16, Output Rly 2 to 8, SelfTest
Rly, Vir Outpt 1 to 5, Disabled