EasyManua.ls Logo

GE Multilin 745

GE Multilin 745
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Overview
http://www.GEindustrial.com/multilin
2–4
GE Multilin
Specifications745
Transformer Management Relay
Specifications
Applicability Transformers: 2 Winding or 3 Winding
Frequency: 50 or 60 Hz nominal
(frequency tracking allows
operation from 2 to 65 Hz)
Inputs CONTROL POWER
Options: LO/HI (specified when
ordering)
LO range: 20 to 60 V DC;
20 to 48 V AC at 48 to 62 Hz
HI range: 90 to 300 V DC;
70 to 265 V AC at 48 to 62 Hz
Power: 30 VA nominal, 40 VA max.
Fuse (not accessible)
Current Rating: 3.15 A
Typ e: 5 × 20 mm Slow-Blow
Littelfuse, High Breaking
Capacity; Model # 2153.15
PHASE CURRENT INPUT
Source CT: 1 to 50000 A primary
1 or 5 A secondary
Relay input: 1 A or 5 A (specified at order)
Burden: Less than 0.2 VA at rated load
per phase
Conversion range: 0.02 to 46 × CT
Accuracy:
at < 4 × CT: ±0.25% of 4 × CT (±0.01 ×CT)
at 4 × CT: ±0.5% of 46 × CT (±0.2 × CT)
Overload withstand: 1 second at 80 times
rated current; 2 seconds at 40
times rated current;
continuous at 3 times rated
current
GROUND CURRENT INPUT
Source CT: 1 to 50000 A primary
1 or 5 A secondary
Relay input: 1 A or 5 A (specified at order)
Burden: less than 0.2 VA at rated load
Conversion range: 0.02 to 46 × CT
Accuracy:
at < 4 × CT: ±0.25% of 4 × CT (±0.01 ×CT)
at 4 × CT: ±0.5% of 46 × CT (±0.2 × CT)
Overload Withstand: 1 second at 80 times
rated current; 2 seconds at 40
times rated current;
continuous at 3 times rated
current
VOLTAGE INPUTS
Source VT: 2 to 600 kV / 60 to 120 V
Source VT ratio: 1 to 5000 in steps of 1
Relay Input: 60 V to 120 V phase-neutral
Burden: Less than 0.025 VA at 120 V
Max. continuous: 273 V
Accuracy: ±1% of 2 × VT (±0.02 × VT)
LOGIC INPUTS
Number of inputs: 16
Dry contacts: 1000 maximum ON
resistance (32 V DC at 2 mA
provided by the 745)
Wet contacts: 30 to 300 V DC at 1.5 mA
ANALOG INPUT
Type: DC mA
Ranges: 0 to 1 mA, 0 to 5 mA, 0 to 10
mA, 0to20mA, 4to20 mA
(programmable)
Input impedance: 375 ±10%
Conversion range: 0 to 21 mA
Accuracy: ±1% of full scale (based on
input range)
TAP POSITION
Type: resistance (ohms)
Range: 0 to 500 or 0.5 to 5.0 k
Bias current: 1 mA or 10 mA (based on
input range)
Accuracy: ±1% of full scale (based on
input range)
RTD
Type: 3 wire
RTD Type 100 Platinum (DIN.43760),
100 Nickel, 120 Nickel
IRIG-B INPUT
Amplitude-modulated: 1.0 to 10 V pk-pk
DC shift: TTL
Input impedance: 70 to 100 k

Table of Contents