S5 Outputs
745
Transformer Management Relay
Setpoints
http://www.GEindustrial.com/multilin
5–89
GE Multilin
that the Trip LED remains on until a reset command is issued (or automatically
after one week). The Alarm LED turns off automatically when the output is no
longer operated.
• OUTPUT 1(8) FLEXLOGIC 01 to 20: The 20 messages shown in the table
below are the parameters of the FlexLogic™ equation for Output 1(8) as
described in the introduction to FlexLogic™.
FIGURE 5–48: Output Relays Scheme Logic
Table 5–13: Output Relay Default FlexLogic™
FlexLogic™
Gate
Output Relay Number
1 to 345678
01 Percent Diff OP Volts/Hertz 1
OP
W1 THD Level
OP
Underfreq 1 OP Underfreq 2 OP Freq Decay 3
OP
02 Inst Diff OP Volts/Hertz 2
OP
W2 THD Level
OP
Freq Decay R1
OP
Freq Decay R2
OP
END
03 Any W1 OC OP OR (2 inputs) Xfmr Overload
OP
OR (2 inputs) OR (2 inputs) END
04 Any W2 OC OP END 5th HarmLevel
OP
END END END
05 OR (4 inputs) END OR (4 inputs) END END END
06 to 20 END END END END END END