GE Multilin G60 Generator Protection System 5-91
5 SETTINGS 5.4 SYSTEM SETUP
5
b) BASIC CONFIGURATION
PATH: SETTINGS PRODUCT SETUP SYSTEM SETUP PHASOR MEASUREMENT BASIC CONFIGURATION PMU1
PMU 1 BASIC
CONFIGURATION
PMU 1
FUNCTION: Disabled
Range: Enabled, Disabled
Default: Disabled
MESSAGE
PMU 1 ID CODE:
1
Range: 1 to 65534 in steps of 1
Default: 1
MESSAGE
PMU 1 STN:
GE-UR-PMU
Range: 16 -character ASCII string
Default: GE-UR-PMU
MESSAGE
PMU 1 SIGNAL SOURCE:
SRC 1
Range: Available signal sources
Default: SRC 1
MESSAGE
PMU 1 CLASS:
Class M
Range: None, Class M, Class P
Default: Class M
MESSAGE
PMU 1 FORMAT:
Integer
Range: Integer, Floating Point
Default: Integer
MESSAGE
PMU 1 STYLE:
Polar
Range: Polar, Rectangular
Default: Polar
MESSAGE
PMU 1 RATE:
10
Range: 1, 2, 4, 5, 10, 12, 15, 20, 25, 30, 60, 100, 120
Default: 10
MESSAGE
PMU 1 PHS-1:
Va
Range: Available synchrophasor values
Default: Va
MESSAGE
PMU 1 PHS-1
NM: GE-UR-PMU-PHS-1
Range: 16 -character ASCII string
Default: GE-UR-PMU-PHS-1
MESSAGE
PMU 1 PHS-14:
Va
Range: Available synchrophasor values
Default: Va
MESSAGE
PMU 1 PHS-14:
NM: GE-UR-PMU-PHS-14
Range: 16 -character ASCII string
Default: GE-UR-PMU-PHS-14
MESSAGE
PMU 1 A-CH-1:
Off
Range: Available FlexAnalog values
Default: Off
MESSAGE
PMU 1 A-CH-1:
NM: AnalogChannel1
Range: 16 -character ASCII string
Default: AnalogChannel1
MESSAGE
PMU 1 A-CH-16 (16):
Off
Range: Available FlexAnalog values
Default: Off
MESSAGE
PMU 1 A-CH-16 (16):
NM: AnalogChannel16
Range: 16 -character ASCII string
Default: AnalogChannel16
MESSAGE
PMU 1 D-CH-1:
Off
Range: Available FlexLogic™ operands
Default: Off
MESSAGE
PMU 1 D-CH-1
NM: DigChannel1
Range: 16 character ASCII string
Default: DigChannel1
MESSAGE
PMU 1 D-CH-1
NORMAL STATE: Off
Range: Off, On
Default: Off