GE Multilin G60 Generator Protection System 5-95
5 SETTINGS 5.4 SYSTEM SETUP
5
c) AGGREGATORS
PATH: SETTINGS  PRODUCT SETUP  SYSTEM SETUP PHASOR MEASUREMENT PMU AGGREGATORS 1
PMU AGGREGATOR1 IDCODE: This setting specifies an IDCODE for the aggregator. Individual PMU data streams
transmitted over this port are identified via their own IDCODES, as per the PMU IDCODE settings. This IDCODE is to
be used by the command frame to start/stop transmission, and request configuration.
PMU AGGREGATOR1 PROTOCOL: This setting selects if C37.118 or the new IEC61850 standard will be used. In
firmware release 6.0 only C37.118 will be available.
PMU AGGREGATOR1: TCP PORT: This setting selects the TCP port number that will be used by this aggregator for
network reporting. When using more than one aggregator, the default value of the port must be properly changed to
avoid port number collisions.
PMU AGGREGATOR1 UDP PORT: This setting selects the UDP port number that will be used by this aggregator for
network reporting. When using more than one aggregator, the default value of the port must be properly changed to
avoid port number collisions.
PMU AGGREGATOR1 PDC CONTROL: The synchrophasor standard allows for user-defined controls originating at
the PDC, to be executed on the PMU. The control is accomplished via an extended command frame. The relay
decodes the first word of the extended field, EXTFRAME, to drive 16 dedicated FlexLogic operands. Each aggregator
supports 16 FlexLogic operands as shown in table 2. The operands are asserted for 5 seconds following reception of
the command frame. If the new command frame arrives within the 5 second period, the FlexLogic operands are
updated, and the 5 second timer is re-started. This setting enables or disables the control. When enabled, all 16 oper-
ands for each aggregator are active; when disabled all 16 operands for each aggregator remain reset.
PMU 1
AGGREGATORS
PMU AGGREGATOR 1
MESSAGE
PMU AGGREGATOR 1:
IDCODE: 1
Range: 1 to 65534 in steps of 1
MESSAGE
PMU AGGREGATOR 1
PROTOCOL: None
Range: None, C37.118
MESSAGE
AGGREGATOR1: TCP Port
NONE
Range: None, 4712, 4713, 4714, 4715, 4716, 4717,
4718, 4719
MESSAGE
AGGREGATOR1: UDP Port
NONE
Range: None, 4712, 4713, 4714, 4715, 4716, 4717,
4718, 4719
MESSAGE
PMU AGGREGATOR 1
PDC CONTROL: Disabled
Range: Disabled, Enabled
MESSAGE
PMU AGGREGATOR1
INCLUDE PMU1: No
Range: No, Yes
MESSAGE
PMU AGGREGATOR1
INCLUDE PMU2: No
Range: No, Yes
MESSAGE
PMU AGGREGATOR1
INCLUDE PMU3: No
Range: No, Yes
MESSAGE
PMU AGGREGATOR1
INCLUDE PMU4: No
Range: No, Yes