B-38 G60 Generator Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
79A6 PMU 1 Current Trigger Pickup 0.1 to 30 pu 0.001 F001 1800
79A7 PMU 1 Current Trigger Pickup Time 0 to 600 s 0.01 F001 10
79A8 PMU 1 Current Trigger Dropout Time 0 to 600 s 0.01 F001 100
79A9 PMU 1 Current Trigger Block (3 items) 0 to 65535 --- 1 F300 0
79AC PMU 1 Current Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
79AD PMU 1 Current Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
Phasor Measurement Unit df/dt Trigger (Read/Write Setting)
79C9 PMU 1 df/dt Trigger Function 0 to 1 --- 1 F102 0 (Disabled)
79CA PMU 1 df/dt Trigger Raise 0.1 to 15 Hz/s 0.01 F001 25
79CB PMU 1 df/dt Trigger Fall 0.1 to 15 Hz/s 0.01 F001 25
79CC PMU 1 df/dt Trigger Pickup Time 0 to 600 s 0.01 F001 10
79CD PMU 1 df/dt Trigger Dropout Time 0 to 600 s 0.01 F001 100
79CE PMU 1 df/dt Trigger Block (3 items) 0 to 65535 --- 1 F300 0
79D1 PMU 1 df/dt Trigger Target 0 to 2 --- 1 F109 0 (Self-reset)
79D2 PMU 1 df/dt Trigger Events 0 to 1 --- 1 F102 0 (Disabled)
79D3 ...Repeated for PMU 2
79DD ...Repeated for PMU 3
79E7 ...Repeated for PMU 4
Field Current Protection Settings (Read/Write Setting)
7A60 Field Current Function 0 to 1 --- 1 F102 0 (Disabled)
7A61 Field Current Origin 0 to 48 --- 1 F151 0 (None)
7A62 Field Current OC Pickup 0.05 to 1 pu 0.01 F001 80
7A63 Field Current OC Delay 0 to 600 s 0.01 F001 100
7A64 Field Current UC Pickup 0.05 to 1 pu 0.01 F001 20
7A65 Field Current UC Delay 0 to 600 s 0.01 F001 100
7A66 Reserved --- --- --- F001 0
7A67 Field Current Target 0 to 2 --- 1 F109 0 (Self-reset)
7A68 Field Current Events 0 to 1 --- 1 F102 0 (Disabled)
Field Ground Protection Settings (Read/Write Setting)
7A6A Field Ground Function 0 to 1 --- 1 F102 0 (Disabled)
7A6B Field Ground Injection Frequency 0.1 to 3 Hz 0.01 F001 100
7A6C Field Ground Inj Connection Type 0 to 1 --- 1 F613 0 (Single Point)
7A6D Field Ground STG1 Pickup 1 to 500 kohms 1 F001 20
7A6E Field Ground STG1 Delay 0.1 to 600 s 0.1 F001 100
7A6F Field Ground STG2 Pickup 1 to 500 kohms 1 F001 5
7A70 Field Ground STG2 Delay 0.1 to 600 s 0.1 F001 30
7A71 Field Ground UC Pickup 0.05 to 100 mA 0.01 F001 100
7A72 Field Ground UC Delay 0.1 to 600 s 0.01 F001 100
7A73 Field Ground Block 0 to 65535 --- 1 F300 0
7A74 Field Ground Target 0 to 2 --- 1 F109 0 (Self-reset)
7A75 Field Ground Events 0 to 1 --- 1 F102 0 (Disabled)
User Programmable Pushbuttons (Read/Write Setting) (16 modules)
7B60 User Programmable Pushbutton 1 Function 0 to 2 --- 1 F109 2 (Disabled)
7B61 User Programmable Pushbutton 1 Top Line --- --- --- F202 (none)
7B6B User Programmable Pushbutton 1 On Text --- --- --- F202 (none)
7B75 User Programmable Pushbutton 1 Off Text --- --- --- F202 (none)
7B7F User Programmable Pushbutton 1 Drop-Out Time 0 to 60 s 0.05 F001 0
7B80 User Programmable Pushbutton 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
7B81 User Programmable Pushbutton 1 Events 0 to 1 --- 1 F102 0 (Disabled)
7B82 User Programmable Pushbutton 1 LED Operand 0 to 65535 --- 1 F300 0
7B83 User Programmable Pushbutton 1 Autoreset Delay 0 to 600 s 0.05 F001 0
7B84 User Programmable Pushbutton 1 Autoreset Function 0 to 1 --- 1 F102 0 (Disabled)
7B85 User Programmable Pushbutton 1 Local Lock 0 to 65535 --- 1 F300 0
7B86 User Programmable Pushbutton 1 Message Priority 0 to 2 --- 1 F220 0 (Disabled)
Table B–9: MODBUS MEMORY MAP (Sheet 31 of 59)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT