B-48 G60 Generator Protection System GE Multilin
B.4 MEMORY MAPPING APPENDIX B
B
A908 Frequency Rate of Change 1 Events 0 to 1 --- 1 F102 0 (Disabled)
A909 Frequency Rate of Change 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
A90A Frequency Rate of Change 1 Trend 0 to 2 --- 1 F224 0 (Increasing)
A90B Frequency Rate of Change 1 Pickup 0.1 to 15 Hz/s 0.01 F001 50
A90C Frequency Rate of Change 1 OV Supervision 0.1 to 3 pu 0.001 F001 700
A90D Frequency Rate of Change 1 Reserved (3 items) 0 to 1 --- 1 F001 0
A910 ...Repeated for Frequency Rate of Change 2
A920 ...Repeated for Frequency Rate of Change 3
A930 ...Repeated for Frequency Rate of Change 4
Restricted Ground Fault (Read/Write Grouped Setting) (6 modules)
A960 Restricted Ground Fault 1 Function 0 to 1 --- 1 F102 0 (Disabled)
A961 Restricted Ground Fault 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
A962 Restricted Ground Fault 1 Pickup 0.005 to 30 pu 0.001 F001 80
A963 Restricted Ground Fault 1 Slope 0 to 100 % 1 F001 40
A964 Restricted Ground Fault 1 Delay 0 to 600 s 0.01 F001 0
A965 Restricted Ground Fault 1 Reset Delay 0 to 600 s 0.01 F001 0
A966 Restricted Ground Fault 1 Block --- --- --- F001 0
A967 Restricted Ground Fault 1 Target 0 to 2 --- 1 F109 0 (Self-reset)
A968 Restricted Ground Fault 1 Events 0 to 1 --- 1 F102 0 (Disabled)
A969 ...Repeated for Restricted Ground Fault 2
A972 ...Repeated for Restricted Ground Fault 3
A97B ...Repeated for Restricted Ground Fault 4
A984 ...Repeated for Restricted Ground Fault 5
A98D ...Repeated for Restricted Ground Fault 6
IEC 61850 received analog settings (read/write)
AA00 IEC 61850 GOOSE analog 1 default value –1000000 to 1000000 --- 0.001 F060 1000
AA02 IEC 61850 GOOSE analog input 1 mode 0 to 1 --- 1 F491 0 (Default Value)
AA03 IEC 61850 GOOSE analog input 1 units --- --- --- F207 (none)
AA05 IEC 61850 GOOSE analog input 1 per-unit base 0 to 999999999.999 --- 0.001 F060 1
AA07 ...Repeated for IEC 61850 GOOSE analog input 2
AA0E ...Repeated for IEC 61850 GOOSE analog input 3
AA15 ...Repeated for IEC 61850 GOOSE analog input 4
AA1C ...Repeated for IEC 61850 GOOSE analog input 5
AA23 ...Repeated for IEC 61850 GOOSE analog input 6
AA2A ...Repeated for IEC 61850 GOOSE analog input 7
AA31 ...Repeated for IEC 61850 GOOSE analog input 8
AA38 ...Repeated for IEC 61850 GOOSE analog input 9
AA3F ...Repeated for IEC 61850 GOOSE analog input 10
AA46 ...Repeated for IEC 61850 GOOSE analog input 11
AA4D ...Repeated for IEC 61850 GOOSE analog input 12
AA54 ...Repeated for IEC 61850 GOOSE analog input 13
AA5B ...Repeated for IEC 61850 GOOSE analog input 14
AA62 ...Repeated for IEC 61850 GOOSE analog input 15
AA69 ...Repeated for IEC 61850 GOOSE analog input 16
IEC 61850 XCBR configuration (read/write settings)
AB24 Operand for IEC 61850 XCBR1.ST.Loc status 0 to 65535 --- 1 F300 0
AB25 Command to clear XCBR1 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AB26 Operand for IEC 61850 XCBR2.ST.Loc status 0 to 65535 --- 1 F300 0
AB27 Command to clear XCBR2 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AB28 Operand for IEC 61850 XCBR3.ST.Loc status 0 to 65535 --- 1 F300 0
AB29 Command to clear XCBR3 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AB2A Operand for IEC 61850 XCBR4.ST.Loc status 0 to 65535 --- 1 F300 0
AB2B Command to clear XCBR4 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AB2C Operand for IEC 61850 XCBR5.ST.Loc status 0 to 65535 --- 1 F300 0
Table B–9: MODBUS MEMORY MAP (Sheet 41 of 59)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT