GE Multilin G60 Generator Protection System B-49
APPENDIX B B.4 MEMORY MAPPING
B
AB2D Command to clear XCBR5 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AB2E Operand for IEC 61850 XCBR6.ST.Loc status 0 to 65535 --- 1 F300 0
AB2F Command to clear XCBR6 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
IEC 61850 LN name prefixes (read/write settings)
AB30 IEC 61850 logical node LPHD1 name prefix 0 to 65534 --- 1 F206 (none)
AB33 IEC 61850 logical node PIOCx name prefix (72 items) 0 to 65534 --- 1 F206 (none)
AC0B IEC 61850 logical node PTOCx name prefix (24 items) 0 to 65534 --- 1 F206 (none)
AC53 IEC 61850 logical node PTUVx name prefix (13 items) 0 to 65534 --- 1 F206 (none)
AC7A IEC 61850 logical node PTOVx name prefix (10 items) 0 to 65534 --- 1 F206 (none)
AC98 IEC 61850 logical node PDISx name prefix (10 items) 0 to 65534 --- 1 F206 (none)
ACB6 IEC 61850 logical node RBRFx name prefix (24 items) 0 to 65534 --- 1 F206 (none)
ACFE IEC 61850 logical node RPSBx name prefix 0 to 65534 --- 1 F206 (none)
AD01 IEC 61850 logical node RRECx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AD13 IEC 61850 logical node MMXUx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AD25 IEC 61850 logical node GGIOx name prefix (5 items) 0 to 65534 --- 1 F206 (none)
AD34 IEC 61850 logical node RFLOx name prefix (5 items) 0 to 65534 --- 1 F206 (none)
AD43 IEC 61850 logical node XCBRx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AD55 IEC 61850 logical node PTRCx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AD67 IEC 61850 logical node PDIFx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AD73 IEC 61850 logical node MMXNx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
ADE2 IEC 61850 logical node CSWIx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
AE3C IEC 61850 logical node XSWIx name prefix (6 items) 0 to 65534 --- 1 F206 (none)
IEC 61850 XSWI configuration (read/write settings)
AECF Operand for IEC 61850 XSWI1.ST.Loc status 0 to 65535 --- 1 F300 0
AED0 Command to clear XSWI1 OpCnt (operation counter) 0 to 1 --- 1 F126 0 (No)
AED1 Repeated for IEC 61850 XSWI2
AED3 Repeated for IEC 61850 XSWI3
AED5 Repeated for IEC 61850 XSWI4
AED7 Repeated for IEC 61850 XSWI5
AED9 Repeated for IEC 61850 XSWI6
AEDB Repeated for IEC 61850 XSWI7
AEDD Repeated for IEC 61850 XSWI8
AEDF Repeated for IEC 61850 XSWI9
AEE1 Repeated for IEC 61850 XSWI10
AEE3 Repeated for IEC 61850 XSWI11
AEE5 Repeated for IEC 61850 XSWI12
AEE7 Repeated for IEC 61850 XSWI13
AEE9 Repeated for IEC 61850 XSWI14
AEEB Repeated for IEC 61850 XSWI15
AEED Repeated for IEC 61850 XSWI16
AEEF Repeated for IEC 61850 XSWI17
AEF1 Repeated for IEC 61850 XSWI18
AEF3 Repeated for IEC 61850 XSWI19
AEF5 Repeated for IEC 61850 XSWI20
AEF7 Repeated for IEC 61850 XSWI21
AEF9 Repeated for IEC 61850 XSWI22
AEFB Repeated for IEC 61850 XSWI23
AEFD Repeated for IEC 61850 XSWI24
IEC 61850 GGIO4 general analog configuration settings (read/write)
AF00 Number of analog points in GGIO4 4 to 32 --- 4 F001 4
IEC 61850 GGIO4 analog input points configuration settings (read/write)
AF10 IEC 61850 GGIO4 analog input 1 value --- --- --- F600 0
AF11 IEC 61850 GGIO4 analog input 1 deadband 0.001 to 100 % 0.001 F003 100000
Table B–9: MODBUS MEMORY MAP (Sheet 42 of 59)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT