EasyManuals Logo

GE Multilin MM300 User Manual

GE Multilin MM300
77 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
2 MM300 MOTOR MANAGEMENT SYSTEM – QUICKSTART GUIDE
CHAPTER 1: OVERVIEW
Table 1-1: MM300 protection functions
RS485 - Modbus RTU
Ethernet - Modbus TCP/IP
Profibus/DeviceNet
52
27
59 47
METERING
V, A, W, var, VA , PF, Hz
27X
51R
49
37
66 46
50G
51G
49
MOTOR
LOAD
Stator RTDs
Bearing RTDs
Phase CT 3
Ground CT 1
Power Fuse
BUS
MM300
MOTOR MANAGEMENT SYSTEM
Temperature
Thermistor
Control PT
Contactor
Control
fuse
Direct voltage inputs
(690 V AC maximum)
Ambient air
RTD
Expansion module,
two cards per module,
maximum of two modules
38
Optional
three-phase
voltage
card
Options:
Six inputs & two form-A outputs (max 5 cards)
?
?
Three-phase voltage card (max 1 card)
Options:
Three RTDs - 100 ohm Platinum (max 2 cards)
?
?
Four form-C contact outputs (max 4 cards)
853739A2.CDR
Six inputs and two outputs (standard)
Optional RTD card
ANSI device Description
27X Undervoltage, auxiliary input
27 Undervoltage, three-phase
37 Undercurrent and underpower
38 Bearing temperature RTD
46 Current unbalance
47 Voltage phase reversal
49 Thermal overload
50G Ground instantaneous overcurrent
51G Ground time overcurrent
51R Locked/stalled rotor, mechanical jam
59 Overvoltage, three-phase
66 Starts per hour and time between starts

Table of Contents