6. Control Functions and Parameter Settings
6-59
C08-0
Automatic start.
= 1: OFF (The drive starts when run command is given after pre-charging. Run commands
before that the power ON sequence is completed will be ignored)
= 2: ON without pick-up
If the run command is ON at the power ON time, then the drive will start once the pre-
charging is completed.
Power Supply
ON
Precharging
(internal RDY)
RUN
(Run command)
Output frequency
= 3: ON with pick-up (flying start)
If the run command is ON at the power ON time, then the drive will start once the pre-
charging is completed, enabling the pick-up function. This mode is useful to start after a
power interruption.
When the drive is used as vector control with sensor, the pick up is not needed even if
the motor is rotating when the drive re-starts. In this case set C08-0 to 2
Power Supply
Precharging
(internal RDY)
RUN
(Run Command)
Output frequency
Motor Speed
Motor speed
Motor speed search
(Pick-Up)
For V/f control, sensorless control C30-0=1,2,3
(Note) If auto start is used, undervoltage fault will not be detected. However, EC0~3 will
output the undervoltage code.