EasyManuals Logo

GE VAT2000 User Manual

GE VAT2000
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #134 background imageLoading...
Page #134 background image
6. Control Functions and Parameter Settings
6-59
C08-0
Automatic start.
= 1: OFF (The drive starts when run command is given after pre-charging. Run commands
before that the power ON sequence is completed will be ignored)
= 2: ON without pick-up
If the run command is ON at the power ON time, then the drive will start once the pre-
charging is completed.
Power Supply
ON
Precharging
(internal RDY)
RUN
(Run command)
Output frequency
= 3: ON with pick-up (flying start)
If the run command is ON at the power ON time, then the drive will start once the pre-
charging is completed, enabling the pick-up function. This mode is useful to start after a
power interruption.
When the drive is used as vector control with sensor, the pick up is not needed even if
the motor is rotating when the drive re-starts. In this case set C08-0 to 2
Power Supply
Precharging
(internal RDY)
RUN
(Run Command)
Output frequency
Motor Speed
Motor speed
Motor speed search
(Pick-Up)
For V/f control, sensorless control C30-0=1,2,3
(Note) If auto start is used, undervoltage fault will not be detected. However, EC0~3 will
output the undervoltage code.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE VAT2000 and is the answer not in the manual?

GE VAT2000 Specifications

General IconGeneral
BrandGE
ModelVAT2000
CategoryController
LanguageEnglish

Related product manuals