6. Control Functions and Parameter Settings
6-10
Sequence Command
SE S3 S2 S1 S0
Selected
freq.
OFF OFF OFF B11-0
OFF OFF
ON
B11-1
OFF
ON
OFF B11-2
OFF
ON ON
B11-3
ON
OFF OFF B11-4
ON
OFF
ON
B11-5
ON ON
OFF B11-6
ON ON ON
B11-7
Block-B parameters (Extended function constants) list
ApplicationNo. Parameter Unit Default Min. Max. Function
ST V/f VEC PM
B10 – Acceleration/deceleration time
0
1
Acceleration ramp
time-2
Deceleration ramp
time-2
sec
sec
10.0
20.0
0.1
0.1
6000.0
6000.0
This acceleration/deceleration ramp
time is valid when the ramp 2
selection is ON (CSEL=ON).
This is the time to reach the max.
frequency or max. speed from 0
This value can be set x0.1 or x10
units by setting the parameter B10-5
accordingly.
2
3
Acceleration ramp
time for jogging
Deceleration ramp
time for jogging
sec
sec
5.0
5.0
0.1
0.1
6000.0
6000.0
This is the acceleration/deceleration
time value when the JOG sequence
(F JOG, R JOG) is ON.
This value can be set x0.1 or x10
units by setting the parameter B10-5
accordingly.
4 S-shape
characteristics (Ts)
sec 0.0 0.0 5.0 Set to 1/2 of less of the ramp time.
S-type ramp time is allowed by setting
this parameter.
5 Time unit 1. 1. 3. The acceleration/deceleration ramp
time setting unit can be changed by
using a multiplier.
1:
x1;
2:
x0.1;
3:
x10
B11 – Program frequency (speed) setting
0
1
2
3
4
5
6
7
Program frequency
(speed) –0
Program frequency
(speed) –1
Program frequency
(speed) –2
Program frequency
(speed) –3
Program frequency
(speed) –4
Program frequency
(speed) –5
Program frequency
(speed) –6
Program frequency
(speed) –7
%
%
%
%
%
%
%
%
10.00
10.00
10.00
10.00
10.00
10.00
10.00
10.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
100.00
100.00
100.00
100.00
100.00
100.00
100.00
100.00
(1) Binary select mode (B11-8=1)
SE and S3 are not used
(2) Direct select mode (B11-8=2)
When S0 to S3 are all OFF the latest
frequency set value is hold. After
power ON that goes to “0”
8 Selection mode
setting
1. 1. 2. = 1 : Binary mode
= 2 : Direct select mode
Select the program frequency setting
(B11) and program ramp (B41, B42)
selection mode.
Sequence Command
SE S3 S2 S1 S0
Selected
freq.
OFF OFF OFF OFF OFF Latest
value
OFF OFF OFF OFF
ON
B11-0
OFF OFF OFF
ON
OFF B11-1
OFF OFF
ON
OFF OFF B11-2
OFF
ON
OFF OFF OFF B11-3
ON
OFF OFF OFF OFF Latest
value
ON
OFF OFF OFF
ON
B11-4
ON
OFF OFF
ON
OFF B11-5
ON
OFF
ON
OFF OFF B11-6
ON ON
OFF OFF OFF B11-7