EasyManuals Logo

GE VAT2000 User Manual

GE VAT2000
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #86 background imageLoading...
Page #86 background image
6. Control Functions and Parameter Settings
6-11
Block-B parameters (Extended function constants) list
ApplicationNo. Parameter Unit Default Min. Max. Function
ST V/f VEC PM
B13 Local setting
0 Torque setting % 0.0 –300.0 300.0 Torque setting from the keypad

1 Torque ratio 1 setting 1.000 0.001 5.000

2 Torque bias 1 setting % 0.0 –300.0 300.0

3 Torque ratio 2 setting 1.000 –5.000 5.000

4 Double rating speed ratio
setting
% 100.0 0.1 100.0 This sets the torque limit reduction
pattern changeover point. Set as a per-
centage in respect to the base speed.

5 Drooping setting % 0.00 0.00 20.00 By adjusting this parameter, the motor
torque/speed characteristics can be
achieved.

6 ASR gain compensation
in constant power range
% 100.0 0.0 150.0 This sets the ASR P gain
compensation value at the max. speed.
By adjusting this parameter, the ASR
P gain can be compensated in the
constant power range.
If ASR hunting occurs in the constant
power range, (with sensor-less vector
control) set a smaller value.

7 ACR gain compensation
in constant power range
% 100.0 0.0 150.0 This sets the ACR P gain
compensation value at the max. speed.
By adjusting this parameter, the ACR
P gain can be compensated in the
constant power range.

B14 ASR dead band setting
0 ASR dead band setting % 0.0 0.0 100.0 The non-sensitive range of the ASR
input is set.

B15 – Machine time constant setting 2
0 Machine time constant 2 ms 1000. 1. 20000. This is the time to accelerate the
motor + load to the base speed at the
motor rated torque.
This is valid when the sequence input
machine time constant changeover is
ON (MCH = ON).

B17 – V/f middle point
0 Frequency 2 Hz 0.0 0.0
Max.freq.
1 Voltage 2 % 0.0 0.0 100.0
2 Frequency 1 Hz 0.0 0.0
Max.freq.
3 Voltage 1 % 0.0 0.0 100.0
These parameters should be set:
Base frequency
B17-0
B17-2
B17-1
B17-3
B18 – Over current limit
0 Over current limit % 150. 100. 300.
1 Regenerative current
limit
% 10. 5. 300. Set to 10% if there is not DBR.
2 Torque stabilisation gain 1.00 0. 4.00 Increase if the motor vibrates.
3 Over current limit
function gain
0.25 0. 2.00 Decrease if current hunting occurs.
4 Current stabilisation gain 0.25 0. 2.00
5 Over current break-down
prevention gain
1.00 0. 2.00
6 Over current stall pre-
vention time constant
100. 10. 1001. P control will be applied if 1001 is set.
B19 Automatic tuning function
0 Automatic tuning
selection
0. 0. 4 The automatic tuning mode is
selected.
1: Basic tuning for V/f Control
2: Extended tuning for V/f Control
3: Basic tuning for Vector Control
4: Extended tuning for Vector Control


Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE VAT2000 and is the answer not in the manual?

GE VAT2000 Specifications

General IconGeneral
BrandGE
ModelVAT2000
CategoryController
LanguageEnglish

Related product manuals