EasyManuals Logo

GE VAT2000 User Manual

GE VAT2000
184 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #65 background imageLoading...
Page #65 background image
5. Control Input / Output
5-12
5-7-2 Setting the analog input
The analog inputs can be randomly assigned to the internal setting signals given in Table 5-5 by setting
parameters C07-0 to 9 as shown in Fig. 5-7.
For example if C07-0 (speed setting 1) is set to “0” this function is disabled; if it is set to “1” the speed
setting function is fixed at 100%, but if C07-0 is set to “3”, then the speed setting 1 function can be
controlled by terminal board input FSI. More details are given in section 6 (C07 parameter list).
An analog interface option type: U2KV23AD0 is necessary to use the additional analog inputs PAI1 to 3.
Terminal block Internal setting signal
PAI
1
0
2
3
4
5
6
7
Speed setting 1
Y=AX+B+C
Y
C
Panel setting
A, B
X
Speed
setting
U2KV23AD0 Option
Speed setting 2
Speed setting 3
Ratio Interlock bias setting
Traverse center frequency setting
PID feedback setting
Torque setting
C07-0=3
C07-1
C07-2
C07-3
C07-4
C07-5
C07-6=2
C07-7
C07-8
C07-9
Drive torque limiter reduction setting
Regenerative torque limiter reduction setting
Torque bias 1 setting
0%
(Note) 100%
FSV
FSI
AUX
PAI1
PAI2
PAI3
.
(Note) The torque setting is 300% when C07-6 is 1.
Fig. 5-7 Analog input assignment
The sequential ratio operation can be carried out in respect to speed settings 1 to 3. (Refer to 6-5.)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE VAT2000 and is the answer not in the manual?

GE VAT2000 Specifications

General IconGeneral
BrandGE
ModelVAT2000
CategoryController
LanguageEnglish

Related product manuals