118 AFE200 • Instruction Manual
If set to 2 the datum is assigned a 32-bit count.
If set to 3 16 bits on the channel are reserved for the datum, not used.
If set to 4 32 bits on the channel are reserved for the datum, not used.
If set to 5 the datum is assigned a 16-bit count used by MDPLC.
If set to 6 the datum is assigned a 32-bit count used by MDPLC.
If set to 7 the datum is assigned engineering units on a 16-bit integer.
If set to 8 the datum is assigned engineering units on a 32-bit integer.
If set to 9, the datum is assigned a 16-bit integer engineering unit format not in real
time (5-10ms)
If set to 10 the datum is assigned a 32-bit integer engineering unit format or oat for-
mat if the associated parameter is a oat-type parameter not in real time (5-10ms)
Note! If the sys parameter is not assigned, none of the subsequent channels are transferred to the fieldbus,
even if programmed.
Menu PAR Description UM Type FB BIT Def Min Max Acc
14.4.3 4184 Dig Fieldbus S->M1 INT32 32 0 0 0 ERW
14.4.7 4194 Dig Fieldbus S->M2 INT32 32 0 0 0 ERW
14.4.11 4204 Dig Fieldbus S->M3 INT32 32 0 0 0 ERW
14.4.15 4214 Dig Fieldbus S->M4 INT32 32 0 0 0 ERW
14.4.19 4224 Dig Fieldbus S->M5 INT32 32 0 0 0 ERW
14.4.23 4234 Dig Fieldbus S->M6 INT32 32 0 0 0 ERW
14.4.27 4244 Dig Fieldbus S->M7 INT32 32 0 0 0 ERW
14.4.31 4254 Dig Fieldbus S->M8 INT32 32 0 0 0 ERW
14.4.35 4264 Dig Fieldbus S->M9 INT32 32 0 0 0 ERW
14.4.39 4274 Dig Fieldbus S->M10 INT32 32 0 0 0 ERW
14.4.43 4284 Dig Fieldbus S->M11 INT32 32 0 0 0 ERW
14.4.47 4294 Dig Fieldbus S->M12 INT32 32 0 0 0 ERW
14.4.51 4304 Dig Fieldbus S->M13 INT32 32 0 0 0 ERW
14.4.55 4314 Dig Fieldbus S->M14 INT32 32 0 0 0 ERW
14.4.59 4324 Dig Fieldbus S->M15 INT32 32 0 0 0 ERW
14.4.63 4334 Dig Fieldbus S->M16 INT32 32 0 0 0 ERW
If associated with the relative src, the value of this parameter is sent to the bus.
The user may modify the M->S and by S->M sys parameters. The consistency of the
sys with the parameter assigned to the channel is checked.
Check for channels S->M:
Sys parameter FB type result
Count 32 32 bit Sends all 32 bits of input to eldbus. OK
16_H Sends all 32 bits of input to eldbus. OK
16_L Sends all 32 bits of input to eldbus. OK
Count 16 32 bit Doesn’t know whether to send 16H or 16L. Error
16_H Sends all 16H bits of input to eldbus. OK
16_L Sends all 16L bits of input to eldbus. OK
Menu PAR Description UM Type FB BIT Def Min Max Acc
14.4.4 4186 Fieldbus S->M1 mul FLOAT 1.0 1.0 1000.0 ERW