AFE200 • Instruction Manual 145
10 - Specication
10.1 Environmental Conditions
Installation location ������������������Pollution degree 2 or lower (free from direct sunligth, vi-
bration, dust, corrosive or inflammable gases, fog, vapour
oil and dripped water, avoid saline environment)
Installation altitude ������������������Max 2000m (6562 feet) above sea level;.
Mechanical conditions for installation ���Vibrational stress: EN 60721-3-3 Class 3M1
Operating temperature ��������������-10…+40°C (32°…104°F)
Operating temperature (1) ������������+40 ... +50°C with derating, (+104 … +122°F with
derating)
Air humidity (operating) ��������������5 % to 85 % and 1 g/m
3
to 25 g/m
3
without moisture
condensation or icing (class 3K3 as per EN50178)
Air pressure (operating) [kPa] ����������86 to 106 (class 3K3 as per EN50178)
(1) In menu 4 - DRIVE CONFIG set the Ambient temperature parameter, PAR 564, to 1 (50°C).
10 % derating of output current.
10.2 Standards
Climatic conditions ������������������EN 60721-3-3
Electrical safety ��������������������EN 50178, EN 61800-5-1, UL508C, UL840 degree of
pollution 2
Vibration ��������������������������EN 60068-2-6, test Fc.
EMC compatibility �������������������EN61800-3
Protection degree �������������������Sizes 3.. 6: IP20;
Size 7: IP00 (with protection against accidental contact)
Approvals ������������������������� ,
OnProgress(*)
(*) Sizes AFE200-...-6/6A with 575 V power supply UL-marked is ON PROGRESS , those with 690 V
power supply are not UL-marked..
10.3 Accuracy
10.3.1 Current control
Loop sampling time ������������������62,5µs
Response time ����������������������800 - 1000µs
PWM frequency ���������������������2, 3, 4, 6, 8 kHz (size dependent)
10.3.2 Voltage control
Loop sampling time �������������������62,5µs
Response time ����������������������10 - 15ms
10.3.3 Current rating
Heavy duty (HD) ���������������������150% 60 sec, 180% 0.5 sec.
Light duty (LD) ����������������������110% 60 sec.
Switching frequency mode (LD) ����������2, 3 or 4 kHz, size dependent
Switching frequency mode (HD) ���������2, 3, 4, 6, 8 kHz

Table of Contents