AFE200 • Instruction Manual 167
> Choosing the power supply unit:
L’ AFE200 selezionato deve essere in grado di fornire un valore di corrente ≥ 220A
Dalla sezione 10.6 seleziono la taglia che rientra nelle caratteristiche :
AFE200-61320.
The AFE200 must be capable of delivering a current of ≥ 220 A
Choose the size with the appropriate characteristics from the section 10.6:
AFE200-61320.
> Choosing the drive:
Choose the size with the rated current required by the motor (≥ 236A) from the
catalogue (section ADV200-DC “2.7 Output Data” on page 37):
With a 650 Vdc drive:
ADV-71600-...-DC (In = 270A, OK).
Drive Description Code Q.ty
ADV200-DC ADV-61320-KXX-4-DC S9O19DC 1
AFE + components Description Code
AFE regenerative AFE200-61320-KXX-4 S9AF04 1
Line chokes LR3-280-500-0,32 S7AL03 1
EMI lter EMI FN3120 -480V-230A S74EE 1
Pre-charge kit PRE CHARGE KIT-AFE-132-4 S726401 1
Fuses mains side connection F4G30 3
Checking total DC-link capacity:
AFE200-61320 with ADV-71600-...-4-DC = 13600 + 16800 = 30400 μF ≤ 30000 +5%
μF (OK)
A1.2 Calculation for multi-motor system
Mains: Vmains = three-phase 400Vac
Motor 1: Poutm = 18.5kW
voutm = 400vca
ηm = 0.95
Im = 37a
Application: continuous load, Pcont= 85%
Requested overload = 150%
Motor 2: Poutm = 18.5kW
voutm = 400vca
ηm = 0.95
Im = 37a
Application: continuous load, Pcont = 90%
Requested overload = 150%
Motor 3: Poutm = 22kW