AFE200 • Instruction Manual 9
1.4 Instruction for compliance with UL Mark (UL require-
ments), U.S. and Canadian electrical codes
Short circuit ratings
AFE200 must be connected to a grid capable of supplying a symmetrical short-
circuit power of less than or equal to “xxxx A rms (at 480 V +10% V max).
The values of the “xxxx” A rms short-circuit current, in accordance with UL require-
ments (UL 508 c), for each power rating (AFE output in the manual) are shown in
the table below.
Short current rating
AFE output (kW) SCCR ( A ) @480Vac
1,1...37,3 5000
39....149 10000
150....398 18000
299.....447 30000
448-671 42000
672-1193 85000
1194 100000 ... 200000
Note! Drive will be protected by semiconductor Fuse type as specified in the instruction manual.
Branch circuit protection
In order to protect drive against over-current use fuses specied in par. 11.1.
Environmental condition
The drive has to be considered “Open type equipment”. Max surrounding air
temperature equal to 40°C. Pollution degree 2.
Wiring of the input and output power terminals
Use UL listed cables rated at 75°C and round crimping terminals. Crimp terminals
with tool recommended by terminal manufacturer.
Field wiring terminals shall be used with the tightening torque specied in par.
5.1.1.
Over-voltage control
In compliance with CSA-requirements Overvoltage at mains terminal is achieved
installing an overvoltage protection device as for :
Type OVR 1N 15 320 from ABB or similar.
Minimum time required for safe DC-link voltage
Before removing drive cover in order to access internal parts, after mains discon-
nection wait for time as follow :
Drive size Safe time ( sec )
size 3.....5 300
size 6...7 and Parallels 300