AFE200 • Instruction Manual 25
710kW
73550-KXX-4/4A-MS 07
2 x 185 2 x kcmil 350 M10 (U,V,W=M12) 50 (M10) / 75 (M12)
73550-XXX-4/4A-SL
2 x 185 2 x kcmil 350 M10 (U,V,W=M12) 50 (M10) / 75 (M12)
900kW
73150-KXX-4/4A-MS 09
2 x 185 2 x kcmil 350 M10 (U,V,W=M12) 50 (M10) / 75 (M12)
73150-XXX-4/4A-SL
2 x 185 2 x kcmil 350 M10 (U,V,W=M12) 50 (M10) / 75 (M12)
73150-XXX-4/4A-SL
2 x 185 2 x kcmil 350 M10 (U,V,W=M12) 50 (M10) / 75 (M12)
1MW
AFE200-73550-KXX-4/4A-MS 10
2 x 185 2 x kcmil 350 M10 (U,V,W=M12) 50 (M10) / 75 (M12)
AFE200-73550-XXX-4/4A-SL
2 x 185 2 x kcmil 350 M10 (U,V,W=M12) 50 (M10) / 75 (M12)
AFE200-73550-XXX-4/4A-SL
2 x 185 2 x kcmil 350 M10 (U,V,W=M12) 50 (M10) / 75 (M12)
Sizes
Terminals: on mechanical cabinet
Recommended cable cross-
section
Lock screw
diameter
Recommen-
ded stripping
Tightening
torque (min)
(mm
2
) AWG / kcmil (mm) (mm) (Nm)
400kW
72000-KXX-4-MS 04 150 300 kcmil M10 Occhiello 50
72000-XXX-4-SL 150 300 kcmil M10 Occhiello 50
500kW
72500-KXX-4-MS 05 150 300 kcmil M10 Occhiello 50
72500-XXX-4-SL 150 300 kcmil M10 Occhiello 50
630kW
73150-KXX-4/4A-MS 06 185 350 kcmil M10 Occhiello 50
73150-XXX-4/4A 4-SL 185 350 kcmil M10 Occhiello 50
710kW
73550-KXX-4/4A-MS 07 185 350 kcmil M10 Occhiello 50
73550-XXX-4/4A-SL 185 350 kcmil M10 Occhiello 50
900kW
73150-KXX-4/4A-MS 09 185 350 kcmil M10 Occhiello 50
73150-XXX-4/4A-SL 185 350 kcmil M10 Occhiello 50
73150-XXX-4/4A-SL 185 350 kcmil M10 Occhiello 50
1MW
AFE200-73550-KXX-4/4A-MS 10 185 350 kcmil M10 Occhiello 50
AFE200-73550-XXX-4/4A-SL 185 350 kcmil M10 Occhiello 50
AFE200-73550-XXX-4/4A-SL 185 350 kcmil M10 Occhiello 50
5.1.2 EMC guide line
Drives are designed to operate in an industrial environment where a high level
of electromagnetic interference are to be expected. Proper installation practices
will ensure safe and trouble-free operation. If you encounter problems, follow the
guidelines which follow.
- Check for all equipment in the cabinet are well grounded using short, thick
grounding cable connected to a common star point or busbar. Better solution
is to use a conductive mounting plane and use that as EMC ground reference
plane.
- Flat conductors, for EMC grounding, are better than other type because they
have lower impedance at higher frequencies.
- Make sure that any control equipment (such as a PLC) connected to the
AFE200 is connected to the same EMC ground or star point as the AFE200
via a short thick link.
- Separate the control cables from the power cables as much as possible, using
separate trunking, if necessary at 90º to each other.
- Whenever possible, use screened leads for the connections to the control
Attention