26 AFE200 • Instruction Manual
circuitry.
- Ensure that the contactors in the cubicle are suppressed, either with R-C
suppressors for AC contactors or ‘ywheel’ diodes for DC contactors tted to
the coils. Varistor suppressors are also effective. This is important when the
contactors are controlled from the AFE200 relay.
- Use screened or armored cables for the U-V-W connections and ground the
screen at both ends using the cable clamps
- Use the recommended EMI lters, which are listed in section 11.3 of this
manual (conformity with EN61800-3, class C3 with 50 metres of motor cable
with a single inverter supplied by the AFE200).
- Use shielded cables in motors to ensure the correct operation of the EMI lter.
Note! For further information regarding electro-magnetic compatibility standards, according to Directive
89/336/EEC, conformity checks carried out on Gefran appliances, connection of filters and mains
inductors, shielding of cables, ground connections, etc., consult the “Electro-magnetic compatibility
guide” on the CD attached to this drive.