32 AFE200 • Instruction Manual
5.1.6 Connection of fans power suplly
Sizes AFE200-
3220 ... 61320 No connection is necessary: the drive’s internal power supply unit powers the fan (+24Vdc).
Sizes AFE200-
Terminals
U3 V3 PE 31 32
71600 ... 72500
1 x 230V / 50/60Hz, 3,5Arms Ground 250V/10A contact (*)
Power the internal fan (max 600W) with a single-phase voltage on terminals U3/V3.
Sizes AFE200-
Terminals
U3 V3 W3 PE 31 32
73150 ... 73550
3 x 400V / 50Hz, 1,55Arms
or
3 x 460V / 60Hz, 1,7Arms
Ground 250V/10A contact (*)
Power the internal fan (max 1200W) with a three-phase voltage on terminals U3/V3/W3.
Sizes
Terminals
U3 V3 PE 31 32
400 kW
500 kW
1 x 230V / 50/60Hz, 3,5Arms
(x 2)
Ground
250V/10A contact (x 2)
(*)
Power the internal fan (max 600W) with a single-phase voltage on terminals U3/V3. ( x 2).
Sizes
Terminals
U3 V3 W3 PE 31 32
630 kW
710 kW
3 x 400V / 50Hz, 1,55Arms (x 2)
or
3 x 460V / 60Hz, 1,7Arms (x 2)
Ground
250V/10A contact (x 2)
(*)
Power the internal fan (max 1200W) with a three-phase voltage on terminals U3/V3/W3. (x 2).
900 kW
1000 kW
3 x 400V / 50Hz, 1,55Arms (x 3)
or
3 x 460V / 60Hz, 1,7Arms (x 3)
Ground
250V/10A contact (x 3)
(*)
Power the internal fan (max 1200W) with a three-phase voltage on terminals U3/V3/W3 (x 3).
(*) Open = Fan stopped; Closed = Fun running (def.)
(**) On AFE200-73150-KXX-6A and AFE200-73550-KXX-6A models.