24 AFE200 • Instruction Manual
5.1 Power section
5.1.1 Cable Cross Section
Sizes
AFE200-
Terminals: C - D - U - V - W
Maximum Cable Cross Section (flexible conductor) Recommended stripping Tightening torque (min)
(mm
2
) AWG (mm) (Nm)
3220 16 6 14 1,5 ... 1,7
4450 35 2 18 2,4 ... 4,5
5900 95 4/0 23 14
61320 240 500 40 40
Bars: C - D - U - V - W
Recommended cable cross-section Recommended stripping Tightening torque (min)
(mm
2
) AWG / kcmil (mm) (Nm)
71600 2 x 100 2 x AWG 4/0 M10 50
72000 2 x 100 2 x AWG 4/0 M10 50
72500 2 x 150 2 x kcmil 300 M10 50
73150 2 x 185 2 x kcmil 350 M10 50
73550 2 x 185 2 x kcmil 350 M10 50
Sizes
AFE200-
Terminals: on mechanical cabinet
Cable Cross Section Lock screw
diameter
Recommended
terminal
Tightening torque
(mm
2
) AWG / kcmil (mm) (mm) (Nm)
3220 ... 4450 16 AWG 6 M6 Eyelet - Spade 10
5900 50 AWG 1/0 M6 Eyelet - Spade 10
61320 120 250 kcmil M8 Eyelet 24
71600 150 300 kcmil M10 Eyelet 50
72000 150 300 kcmil M10 Eyelet 50
72500 150 300 kcmil M10 Eyelet 50
73150 185 350 kcmil M10 Eyelet 50
73550 185 350 kcmil M10 Eyelet 50
Sizes
AFE200-
Bars: C - D - U - V - W
Recommended cable cross-
section
Recommended
stripping
Tightening torque
(min)
(mm
2
) AWG / kcmil (mm) (Nm)
400kW
72000-KXX-4-MS 04
2 x 100 2 x AWG 4/0 M10 (U,V,W=M12) 50 (M10) / 75 (M12)
72000-XXX-4-SL
2 x 100 2 x AWG 4/0 M10 (U,V,W=M12) 50 (M10) / 75 (M12)
500kW
72500-KXX-4-MS 05
2 x 150 2 x kcmil 300 M10 (U,V,W=M12) 50 (M10) / 75 (M12)
72500-XXX-4-SL
2 x 150 2 x kcmil 300 M10 (U,V,W=M12) 50 (M10) / 75 (M12)
630kW
73150-KXX-4/4A-MS 06
2 x 185 2 x kcmil 350 M10 (U,V,W=M12) 50 (M10) / 75 (M12)
73150-XXX-4/4A 4-SL
2 x 185 2 x kcmil 350 M10 (U,V,W=M12) 50 (M10) / 75 (M12)