146 AFE200 • Instruction Manual
10.4 Overload
Heavy duty (HD) 150% 60 sec every 300 sec, 180% 0,5 sec.
Light duty (LD) 110% 60 sec every 300 sec.
10.5 DC circuit
DC-link voltage rating �����������������
650...780 Vdc (aFE-...-4/4a),
820...1120 Vdc (aFE-...-6/6a)
DC overvoltage threshold ��������������820 Vdc (
aFE-...-4/4a
), 1192 Vdc
(aFE-...-6/6a)
;
DC undervoltage threshold��������������380 Vdc (@ 400 Vac), 676 Vdc (@ 690 Vac);
563 Vdc (@ 575 Vac)
Sizes
AFE200-
DC-link capacity (AFE200-...-4) DC-link capacity (AFE200--...-6)
Internal
(µF)
Maximum
(AFE + Drive)
(µF)
Internal
(µF)
Maximum
(AFE + Drive)
(µF)
3220 1500 10000 - -
4450 3400 10000 - -
5900 6800 30000 - -
61320 13600 30000 - -
71600
16800 80000 11200 80000
72000 16800 80000 11200 80000
72500 25200 80000 11200 80000
73150 25200 80000 11200 80000
73550 25200 80000 11200 80000
400kW 2 x 16800 2 x 80000 2 x 11200 2 x 80000
500kW 2 x 25200 2 x 80000 2 x 11200 2 x 80000
630kW 2 x 25200 2 x 80000 2 x 11200 2 x 80000
710kW 2 x 25200 2 x 80000 2 x 11200 2 x 80000
900kW 3 x 25200 3 x 80000 3 x 11200 3 x 80000
1MW 3 x 25200 3 x 80000 3 x 11200 3 x 80000