AFE200 • Instruction Manual 131
8.1 Parameters on selection lists, but not displayed on
keypad
Menu PAR Description UM Type FB BIT Def Min Max Acc
- 362 Drive overload trip BIT 16BIT 0 0 1 ER
This signal indicates that the AFE product is in the overload alarm condition.
Menu PAR Description UM Type FB BIT Def Min Max Acc
- 366 Drive overload 80% BIT 16BIT 0 0 1 ER
This signal indicates that the AFE product has reached 80% of the thermal image ac-
cumulator (Drive overload).
Menu PAR Description UM Type FB BIT Def Min Max Acc
- 1030 Local/remote mon BIT 16BIT 0 0 1 ER
This signal is active when the AFE product is in the Remote operating mode.
0 Local
1 Remote
Menu PAR Description UM Type FB BIT Def Min Max Acc
- 1062 Drive OK BIT 16BIT 0 0 1 ER
This signal is active when the AFE product is in the “OK” condition and no alarms are
present.
Menu PAR Description UM Type FB BIT Def Min Max Acc
- 1064 Drive ready BIT 16BIT 0 0 1 ER
This signal is active when the AFE product reference is in the “Ready” to run condi-
tion.
Menu PAR Description UM Type FB BIT Def Min Max Acc
- 1068 Enable ready mon BIT 16BIT 0 0 1 ER
This signal is active when the AFE can accept the enable command. If the enable
command is sent before PAR 1068 Enable ready mon is active, it is not accepted.
Menu PAR Description UM Type FB BIT Def Min Max Acc
- 1110 Digital input E mon BIT 16BIT 0 0 1 ER
- 1112 Digital input 1 mon BIT 16BIT 0 0 1 ER
- 1114 Digital input 2 mon BIT 16BIT 0 0 1 ER
- 1116 Digital input 3 mon BIT 16BIT 0 0 1 ER
- 1118 Digital input 4 mon BIT 16BIT 0 0 1 ER
- 1120 Digital input 5 mon BIT 16BIT 0 0 1 ER
These signals represent the state of the corresponding digital input.
Menu PAR Description UM Type FB BIT Def Min Max Acc
- 1122 Precharge Command BIT 16BIT 0 0 1 ER
This signal is enabled when the voltage on the DC-link exceeds the set value and

Table of Contents