148 AFE200 • Instruction Manual
(5) Current values at ambient temperature of 35°C.
(6) Kv : Derating factor for DC power supply (690 V)
(7) Kt : Derating factor for ambient temperature of 50°C (1% every °C over 40°C with HD and 2% every °C over 40°C with LD)
For sizes 73550, 710 kW and1000 kW: Derating factor for ambient temperatures of > 40°C up to 50°C (1% every °C over 35°C with
HD and 2% every °C over 40°C with LD)
(8) Kalt : Derating factor for installation at altitudes above 1000 meters a.s.l.. Value to be applied at each 100 m increase above 1000
m (up to a maximum of 2000 m).
I.e.: Altitude 2000 m, Kalt = 1,2 *10 = 12% di derating; In derated = 100 - ((12*100)/100) = 88 % In
Sizes
AFE200-
AC power
Output AFE-...-4/4A
(@ 400Vac)
Output AFE-...-4/4A
(@ 460Vac)
Output AFE-...-6/6A
(@ 690Vac)
Heavy duty
(KW)
Light duty
(KW)
Heavy duty
(KW)
Light duty
(KW)
Heavy duty
(KW)
Light duty
(KW)
3220 28 42 29 43 - -
4450 55 69 57 72 - -
5900 110 139 115 143 - -
61320 159 194 165 201 - -
71600 194 236 201 244 179 227
72000 236 277 244 287 227 287
72500 277 346 287 358 287 358
73150 346 388 358 402 358 406
73550 388 416 402 430 406 454
400kW 416 527 430 545 430 544
500kW 527 658 545 681 544 681
630kW 658 734 681 760 681 771
710kW 734 797 760 825 771 860
900kW 970 1039 1004 1075 1015 1100
1MW 1039 1200 1075 1242 1100 1374