819XX_MAN_GRM-H_11-2022_ENG_pag. 81
Errors and warnings in the Detailed Device Status
Event
code
Event Description
Event
type
Device status Possible failure
Process data
value
Reset mode
0x8CA1
SSR temperature sensor
broken
Warning
Maintenance
required
The temperature
sensor does not give a
correct value
measured data
Requires intervention on the
hardware
0x8CA2 CT sensor broken
Warning
Maintenance
required
Current sensor does
not provide correct
value
measured data
Requires intervention on the
hardware
0x8CA3 SSR Over heat
Warning
Maintenance
required
The temperature
value is greater
than the maximum
threshold
measured data
Lower the temperature of
the device
0x8CA4 HB alarm
Warning
Maintenance
required
The Hb alarm is on
measured data
Restore the load
0x8CA5 Frequency warning
Warning
Maintenance
required
The mains frequency
is outside the validity
range
measured data
Bring the mains
frequency back within
limits
0x8CA6 SSR_SHORT alarm
Warning
Maintenance
required
The SCR_SHORT
alarm is on
measured data
Restore the load
0x8CA7 NO_CURRENT alarm
Warning
Maintenance
required
NO_CURRENT
alarm on
measured data
Restore the load
0x8CA8 NO_VOLTAGE alarm
Warning
Maintenance
required
NO_VOLTAGE alarm
on
measured data
Restore the load
0x8CAA
SHORT_CIRCUIT_
CURRENT alarm
Warning
Maintenance
required
SHORT_CIRCUIT_
CURRENT alarm on
measured data
Restore the load
Error code
Error
code
Description
0x8000 Device application error - no details
0x8011 Index not available
0x8012 Sub-index not available
0x8022 Service Unavailable - Device Control
0x8023
Access denied
0x8030 Parameter value out of range
0x8031 Parameter value above limit
0x8032 Parameter value below limit
0x8033 Wrong parameter length (overrun)
0x8034 Wrong parameter length (underrun)
0x8035 Function not available
0x8036 Function temporarily unavailable
0x8040
Invalid Parameter Set
0x8041
Inconsistent Parameter Set
Regarding the Detailed Device Status: when an “event appear” occurs, the event is placed in the first available
position.
When the “event disappear” occurs, that position becomes free again. When an event is active and other
positions become free, or when an “event appear” of another type occurs, the event does not change its
occupied position.
If an "event disappear" occurs and then an "event appear" again, the new position occupied may be different
from the one previously occupied (it will occupy the first available one, as written above).
A maximum of four events can be logged in the buffer. The events in excess are not recorded in the buffer (in
any case, the messages relating to the events are always sent).