14 VDL200 • Quick installation guide - Specifications and connection
4.5.2 Derating values for switching frequency


Figure 4.5.2: Ratio between switching frequency/heat sink temperature
5
10
T diss (°C)
F (kHz)
SW
T diss th
4.5.3 Kalt: Ambient temperature reduction factor
󰀩
0.95
1.00
Ta
mb (°C)
K
T
-10 45 50
Function not allowed
Range of ambient temperatures allowed
4.6
Voltage level of the inverter for safe operations
The minimum time between the moment in which an VDL200 inverter is disabled from the mains and that in which an
operator can operate on internal parts of the inverter, without the danger of electric shock, is 5 minutes.
󰀨supplied without any options (time indicated for disabled inverter condition).
4.7
No-load consumption (Energy rating)
Size No. of pre-loads allowed Power-on
time
[secs]
Stand-by consumption
"Fan Off"
[W]
Fan consumption
[W]
Stand-by consumption
"Fan On"
[W]
VDL200-...-4, 3ph
1040 1 each 20 sec. 5 abt. 20 4 24
1055 1 each 20 sec. 5 abt. 20 10 30
2075 1 each 20 sec. 5 abt. 20 10 30
2110 1 each 20 sec. 5 abt. 20 8 28
3150 1 each 20 sec. 5 abt. 20 16 36
3185 1 each 20 sec. 5 abt. 20 15 35
3220 1 each 20 sec. 5 abt. 20 15 35