12.3 Electrical connection with cable gland
Note: Ordering option Option code 0, 2, 4, 6
Position of the connections
X1
X3
X2
Connection X1/X2: M16 cable gland
Connection X3: M12 cable gland
Recommended cable dia-
meter:
X1 / X2: 4 - 10 mm
X3: 3.5 – 7 mm
Terminals: Wago 236
Cross section of wire: 0.5...2.5 mm² / AWG 20…12
Internal wiring:
10V
X
T
Uw+
Iw+
Iw-
Uw-
X+
X-
GND
24V
A1 A2
T
ERR
Key
10 V green
1)
Connection of external travel sensor
X brown
1)
white
1)
I
W
+ Set value input 0 / 4-20 mA
I
W
-
U
W
+ Set value input 0 - 10 V
U
W
-
X+ Actual value output 0 - 10 V
4-20 mA (optional) - internal supply
X-
GND Supply voltage 24 V DC
24 V
Potential earth
A1 Alarm 1
A2 Alarm 2
ERR Error message output
GND out
1) Core colours when using an external travel sensor
GEMÜ 4231 or 4232. Connect in the specified order.
Other external travel sensors may have different core colours.
www.gemu-group.com24 / 71GEMÜ 1435 ePos
12 Electrical connection

Table of Contents