34 LRR 1-52, LRR 1-53, URB 55 - USA - Installation & Operating Manual - 850703-00
Electrical connection of the LRR 1-52, LRR 1-53
Connecting an LRGT 1x-x conductivity transmitter
Use a shielded, multi-core TC-ER control cable with minimum wire size AWG18, e.g., OELFLEX
CONTROL TM CY 5G1.
Connect the conductivity transmitter as shown in the wiring diagram Fig. 18.
Maximum cable length = 328ft (100m).
Route connecting cables separately from power cables.
The conductivity transmitter must be connected to its own dedicated supply voltage.
Connecting the actual value/manipulated variable output (4 - 20mA)
Please note the load resistance of max. 500W.
Use a shielded, multi-core TC-ER control cable with minimum wire size AWG18, e.g., OELFLEX
CONTROL TM CY 3G1.
Maximum cable length = 328ft (100m).
Route connecting cables separately from power cables.
Connecting the standby input (24V DC)
24V DC input, for external command Control OFF, Valve CLOSED, Intermittent blowdown OFF.
Maximum cable length = 98ft (30m).
Connecting the potentiometer (0 - 1000W)
Use a shielded, multi-core TC-ER control cable with minimum wire size AWG18, e.g., OELFLEX
CONTROL TM CY 3G1.
Maximum cable length = 328ft (100m).
Route connecting cables separately from power cables.

Table of Contents

Other manuals for GESTRA LRR 1-52

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GESTRA LRR 1-52 and is the answer not in the manual?

GESTRA LRR 1-52 Specifications

General IconGeneral
BrandGESTRA
ModelLRR 1-52
CategoryController
LanguageEnglish

Related product manuals