2.03.1 Electrical Connections continued
Figure 2.03.1A: 1Ph Hood ... Separate External Appliance Interlock Contactor Details
1. As shown on page 7, a 1phase FSH2PH hood requires a separate, field installed, appliance interlock circuit
with an appropriately sized contactor, connected as shown by this diagram ... customer supplied.
2. Remove upper rear hood panel to gain access to terminal blocks for connecting coil control wiring (P1, P2).
Attach appropriate conduit at cutout and route wiring to the customer supplied appliance interlock
enclosure. Allow enough length (conduit & wire) so that the hood can be moved to access for cleaning and
servicing.
3. Make appropriate connections for appliance power as indicated and reinstall hood back panel.