7.5 Advanced Settings - Technicians Only
NOTE
To access to this area is for fully qualified and accredited technicians only.
Please follow 7.4 to enter password to access this menu.
Select Advanced Settings from the Main Menu to access the following options:
1. Select Standard
2. Switch ON/OFF
3. Clear Energy
4. Reset Password
5. Power Control
6. Calibrate Energy
7. Special Settings
8. STD. Mode Settings
9.Restore Settings
10. HMI Update
11. Restart HMI
12. Fan Test
13. DSP Update
14. Compensation Set
15. I/V Curve
7.5.1 Selecting Standard
Figure 7.16 UL-600V
Selecting the āUser-Defā standard will allow for a custom grid standard setting to be set.
Figure 7.17 UL-800V
OV-G-V1: 880V
OV-G-V1-T: 0.6S
Below is the setting range for āUser-Defā. Using this function, the limits can be changed
manually. (These voltage values are the phase voltage)
This function is used to select the grid's reference standard.
YES=<ENT> NO=<ESC>
Standard:UL-600V
YES=<ENT> NO=<ESC>
Standard:UL-800V
OV-G-V1: 660V
OV-G-V1-T: 0.6S