User Manual
43
NOTE
The initial value of the User-Def standard is for reference only. It does
not represent a correct value suitable for use.
7.5.2 Switch ON/OFF
This function is used to start up or stop the power generation of Solis Three Phase Inverter.
Grid ON
Grid OFF
Figure 7.18 Set Grid ON/OFF
Screens can be scrolled manually by pressing the UP/DOWN keys. Press the ENTER key
to save the setting. Press the ESC key to return to the previous menu.
7.5.2.1 Grid ON/OFF
7.5.2.2 24H-Var Switch
This function is used to disable or enable the reactive power compensation at night.
Enable
Disable
Figure 7.19 Set 24H-Var Switch
Press UP/DOWN to select and press to Enter to save the setting.
Press the ESC to return to the previous menu.
OV-G-V1: 880---960V
OV-G-V1-T: 1---13S
OV-G-V2: 880---1040V
OV-G-V2-T: 0.12S
UN-G-V1: 40---704V
UN-G-V1-T: 2---50S
UN-G-V2: 40---400V
UN-G-V2-T: 0.16---21S
Startup-T: 10-600S
OV-G-F1: 61-66Hz
OV-G-F1-T: 180---1000S
OV-G-F2: 61.8-66Hz
OV-G-F2-T: 0.16---1000S
UN-G-F1: 50-59Hz
UN-G-F1-T: 180---1000S
UN-G-F2: 50-57Hz
UN-G-F2-T: 0.16---1000S
Restore-T: 59-61Hz
Table 7.4 Setting ranges for User-Def (800V for 255K)
7. Normal operation