User Manual
52
5. Reac-power (Not Required)
Description: Inverter will generate reactive power based on changing output power.
Note: This Setting is NOT required by Rule21 Standards.
This function is for maintenance personnel only, wrong operation
will prevent the inverter from reaching maximum power.
YES=<ENT> NO=<ESC>
Power Factor:+1.00
Figure 7.34 Fixed-PF Figure 7.35 PF Range
0,6
0,6
1,0-1,0
P/Pn
under-excited
Q/Pn
under-excited
over-excited
over-excited
III
IV
III
-0,2
Rated 800V Grid
V1:(640-800V) Default 736V V2: (800-960V) Default 848V
V3:(800-960V) Default 880V V4: (800-960V) Default 920V
P1:100% P2:100% P3: 0% P4:0%
Figure 7.33 Volt-VAR
Voltage1:0796V
Voltage2:0880V
4.Fixed-PF
Description: Inverter will output power with fixed power factor.
Setting Range: -0.8 to +0.8
Default value is PF = 1
7. Normal operation