What causes an Abnormal GFCI 30mA error on a Goodwe GW10K-ET Inverter?
- NNicholas CochranSep 1, 2025
An 'Abnormal GFCI 30mA' error on your Goodwe Inverter indicates that the input insulation impedance has become low during operation. If this occurs occasionally, it might be due to a cable issue, and the inverter should recover automatically once the problem is resolved. However, if the problem occurs frequently or persists, check whether the impedance between the PV string and PE is too low.