Advanced Programming
48 332305J
Advanced Programming
There are 11 Advanced Programming options. The following Table Identifies each option and when it is used.
Firmware 6.02 and later
Advanced
Option
Model Setting Format/ Description Why Use This?
A1 Max Lockout
Code (Optional)
Secures setup modes with PIN Prevents unauthorized users to adjusting set-
tings.
A2 Max Low Level Alarm
Time
MM:SS (minutes:seconds) sets
amount of time between Low
Level Warning to Low Level
Fault.
Default = 3 minutes
To accommodate most lubrication situations, a
conservative amount of time is programmed
between the low level warning and fault to help
protect unit from running dry. If necessary the
amount of time the unit runs before stopping due
to a low level fault can be adjusted.
A3 Max Vent Valve Time MM:SS (minutes:seconds) sets
amount of time vent valve stays
open after Pump ON Mode.
Default = 5 minutes
• In an injector based system that does not use
a sensor for feedback, determines the amount
of time the system vents.
• Vent time can be modified.
A4 Max Alarm Retry Sets number of automatic
retries after a Cycle or Pressure
Alarm.
Default = 0
Establishes the number of times the unit auto-
matically retries lubricating after a cycle or pres-
sure alarm to determine if a temporary or false
signal can be cleared.
A5 Max Active Alarm Changes alarm output behav-
ior.
Default = OFF
Uses alarm output to determine if a unit has an
alarm AND/OR loses power.
The output turns ON when power is applied. It
turns OFF when power is lost or an alarm
occurs.
Normal operation (OFF) will only activate alarm
output in an alarm condition when power is on.
Can change (set to ON) to activate alarm with
power ON and deactivate with power OFF OR
warning.
Used to manage power outage.
A6
DMS
™
Equipped
Models
Functional and
Technical User
Summary Reset
Clears the Functional and Tech-
nical User Summaries
Allows user to track lube events from a specific
point (reset), i.e. a month to month evaluation.
A7 Max Constant Alarm
Output on Fault
Changes alarm output behav-
ior.
Default = OFF
This function changes the behavior of the alarm
output in a fault from either toggling once every
second or steady on.
A8 Max 4 Digit Hour Off
Time
Changes maximum OFF time.
Default = OFF
This function changes OFF time from HH:MM to
HHHH. It allows a maximum of 9999 hours of
OFF time.
A9 Max
and
“08” option
Toggle Low Level
Output on Warning
or Fault
Changes Low Level Indication
behavior.
Default = OFF
This function changes the behavior of the low
level output in a warning or fault from either
steady on or toggling once per second.