6.11 Signal cables
Use screened cables with a cross-sectional area of
minimum 0.5 mm
2
and maximum 1.5 mm
2
for the
external on/off switch, digital inputs, setpoint and
sensor signals.
The wires in the motor terminal box must be as short
as possible.
6.11.1 Connecting signal cables
1. Connect the screens of the cables to the frame at
both ends with good connection. The screens
must be as close as possible to the terminals.
TM082967
Model K
2. Connect the signal cables to the terminals.
3. Depending on the model, tighten one or two
terminal screws.
6.12 Bus connection cable
6.12.1 Connecting a 3-core bus cable, GENIbus
For the bus connection, use a screened 3-core cable
with a cross-sectional area of minimum 0.5 mm
2
and
maximum 1.5 mm
2
.
If the motor is connected to a unit with a cable
clamp which is identical to the one on the product,
connect the screen to the cable clamp.
If the unit has no cable clamp, leave the screen
unconnected at this end.
A
Y
B
A
Y
B
TM070223
6.12.2 Connecting a 3-core bus cable, Modbus
A screened, twisted-pair cable must be used. The
cable screen must be connected to protective earth at
both ends.
Recommended connection
Terminal Modbus
Colour
code
Data
signal
A D1 Yellow Positive
B D0 Brown Negative
Y
Common/
GND
Grey
Common/
GND
Fitting the cable
1. Connect the yellow conductor to terminals D1 and
A.
2. Connect the brown conductor to terminals D0 and
B.
3. Connect the grey conductor to terminals
Common/GND and Y.
4. Connect the cable screens to protective earth via
the earth clamp.
D1
GND
D0
A
Y
B
TM083382
It is important to connect the screen to
protective earth through the earth clamp
and to connect the screen to protective
earth in all units connected to the bus line.
27
English (GB)

Table of Contents

Other manuals for Grundfos CRE Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Grundfos CRE Series and is the answer not in the manual?

Grundfos CRE Series Specifications

General IconGeneral
Motor TypeAsynchronous
Enclosure ClassIP55
Insulation ClassF
SeriesCRE
Protection ClassIP55
MaterialStainless Steel
ApplicationsWater Supply, Pressure Boosting, Irrigation
Pumped liquidClean liquids
ApprovalsCE
Voltage380-415V
Connection SizeDN 32 to DN 100
EfficiencyIE3 Premium Efficiency
Power Supply3-phase
Liquid Temperature Range-10°C to +120°C
Temperature Range-10°C to +120°C

Related product manuals