Constant
temperature
K
p
T
i
Heating
system
Cooling
system
0.5 -0.5 30 + 5L2
10)
In heating systems, an increase in pump performance
results in a rise in temperature at the sensor.
11)
In cooling systems, an increase in pump performance
results in a drop in temperature at the sensor.
L2: Distance in metres between the heat exchanger
and the sensor.
Constant differential
temperature
K
p
T
i
-0.5 10 + 5L2
L2: Distance in metres between the heat exchanger
and the sensor.
Constant flow rate
K
p
T
i
0.5 0.5
Constant pressure
K
p
T
i
0.5 0.5
0.5 0.5
Constant level
K
p
T
i
-10 0
Constant level
K
p
T
i
10 0
General rules of thumb:
If the controller is too slow-reacting, increase the
gain.
If the controller is hunting or unstable, dampen the
system by reducing the gain or increasing the integral
time.
Factory setting
See the section on factory settings.
Related information
9.58 Factory settings for Grundfos GO
9.17 Operating range
Set the operating range as follows:
1. Set the minimum speed within the range from
fixed minimum speed (5) to user-set maximum
speed (2).
62
English (GB)