GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 20
There are two ways for using disablement function: basic steps and quick disablement.
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆
Note: Disable status setting will be saved even if the CIE is powered off.
☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆☆
3.3.2 Operation Basic Steps – Generally used for individually Disabling Zones or Sounder
/Alarm Outputs when the panel is in normal operation mode.
1) Enter access Level II as described in Section 3.1.2.
2) Pressing the DISABLE/ENABLE button will illuminate the amber LED directly above it steadily.
At the same time the amber LED of zone 1 will start flashing to show zone 1 is selected for
disablement setup. The DISABLE LED illuminates steadily when any disablement event occurs.
The FAULT LED will indicate according to the CIE fault condition. Other indicators, except for
the above mentioned LEDs, will be turned off.
3) Pressing the SCROLL button will toggle through zones 1 to 16 and the Sounder Outputs.
Please note the Alarm Output is not able to be Disabled.
4) The AMBER LED for zones 1 to 16 will flash when the zone is to be selected. Pressing the
ENTER button will confirm the selection of the zone or output selected. That zone or output is
now Disabled. The illuminating DISABLE LED indicates the zone is disabled for that zone or
output.
5) When disabling Sounder Outputs the SOUNDER X FLT/DIS LED will flash when a sounder
output is to be selected. Pressing the ENTER button will confirm your selection of this output
and disable it. The illuminating DISABLE LED indicates the sounder output selected is disabled.
6) Pressing the ENTER button again can change the disable/enable state of the sounder outputs
and the CIE will give a 1 second sound indication.
7) Pressing the CANCEL button exits the disablement setting status and the DISABLE/ENABLE
LED will be turned off.
8) Exit access level II.
3.3.3 Quick Disablement Function – Generally used for group Disablements of Zones or
Sounder Outputs when the panel is in Alarm mode.
These two buttons DISABLE and DIS/ENABLE WARNING SYSTEM can be used for quick
disablement. The DISABLE button can disable those zones in a fire condition and DIS/ENABLE
WARNING SYSTEM can disable or enable all sounder outputs at the same time.
Please note: The “DIS/ENABLE WARNING SYSTEM” button can also be used in the normal
operation mode.