GST102A/GST104A/GST108A/GST116A
Conventional Fire Alarm Control Panel
Installation and Operation Manual
Page 31
4.2 Acknowledgement and Silence of Fault
A fault condition can be acknowledged and silenced from access level I.
Pressing the SILENCE BUZZER button under a fault condition, the buzzer of the CIE will be
silenced and the fault is acknowledged. FAULT LED will illuminate steadily.
4.3 Acknowledgement and Silence of Fire Alarm
A fire alarm can be acknowledged and silenced from access level I.
Pressing the SILENCE BUZZER button under fire alarm condition, the buzzer of the CIE will be
silenced and the fire alarm is acknowledged. FIRE LED and zone red LED will illuminate steadily.
4.4 Silencing the Sounder Outputs
The Sounder Outputs can be silenced at access level II.
Pressing the SILENCE/RESOUND ALARM button can silence the sounder outputs. In fire
condition, pressing the SILENCE/RESOUND ALARM button again will make them resound.
If the remote SILENCE input contact is shorted for over 2 seconds, the CIE will silence the sounder
outputs regardless of the current access level.
4.5 Evacuation
The evacuation can be operated at access level II.
Pressing the EVAC button, all sounder outputs will be started immediately. Pressing the EVAC
button again, all sounder outputs will be stopped.
If the remote EVAC input contact is shorted for over 2 seconds, the CIE will activate EVAC function
to start all sounder outputs immediately regardless of the current access level.
4.6 Self-test and Reset
Self-test and reset can be carried out at access level II.
The CIE will start self-test on power-up. Pressing the Reset button can clear all audio and visual
indication and carry out self-test. The self-test can check all indicators and the buzzer. All indicators
illuminate and the buzzer sounds. After self-test, the panel returns to normal condition.
If the remote RESET input contact is shorted for over 2 seconds, the CIE will start reset and self-
test regardless of the current access level.