38
CMD600
A2820−1.1 en
CH_INPUT_OFFSET
Used to set input offset for first amplifier (integrator). Value is in DAC quants and
corresponds to +/−3mV. This parameter isn’t changed when factory default is carried out.
command CH_INPUT_OFFSET select_input_offset,input_offset
parameters:
select_input
_ offset
int 0...input offset, when high pass filter is off.
1...input offset for slow high pass filter. 2...input
offset for fast high pass filter..
input_offset int Input offset in quants.
response OK, CH_INPUT_OFFSET = select_input_offset,input_offset
parameters:
select_input
_ offset
int Look decsription above.
input_offset int Input offset in quants.
inquiry CH_ INPUT_OFFSET = ?
response OK, CH_ INPUT_OFFSET = input_offset(HPF off), input_offset(slow HPF),
input_offset(fast HPF)
help CH_ INPUT_OFFSET ?
response OK, CH_ INPUT_OFFSET select_input_offset(0..2),input_offset
(min = −2048, max = 2047)
CH_CAL_DAC
Used for DAC calibration. Sets output dac value in quants.
command CH_CAL_DAC dac_quants
parameters:
dac_quants int DAC quants(0…4095)
response OK, CH_ CAL_DAC = dac_quants
parameters:
dac_quants int See description above.
help CH_ CAL_DAC ?
response OK, CH_ CAL_DAC dac_quants (min = 0, max = 4095)
AD_DATA
Return average last 50 AD
streaming is enabled.
value in quants. This command can not be use when data
command Not applicable
command AD_DATA=?
response OK, AD_DATA = ad_quants
parameters:
ad_quants int Average last 50 AD converter value in quants.
help AD_DATA?
response OK, AD_DATA