EasyManuals Logo
Home>Higen>Servo Drives>FDA7002EX

Higen FDA7002EX User Manual

Default Icon
214 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #156 background imageLoading...
Page #156 background image
5. Servo operating
4-25
4.6.2. Absolute value encoder initialization
1) When the absolute value encoder requires initialization
- During first operation
- When the encoder cable is separate from the servo drive
- After replacing the battery
- When the absolute encoder related alarm is generated
2) Absolute value encoder initialization (reset) method
- 17bit serial absolute value encoder: When it sets the origin by itself, set the parameter
(P01-20) to “ON” and it will change to “ON =>OFF” to initialize the current position. (Multi-
Turn data reset). When the absolute value related alarm is generated, execute alarm reset
by using alarm reset contact point (ALMRST).
- When it sets the origin by itself, set the parameter (P01-20) to “ON” and it will change to
“ON =>OFF” to initialize the current position. Or connect the power to encoder terminal
ERST (CN2-20) and Vcc terminal (CN2-19) for more than 4 seconds.

Table of Contents

Questions and Answers:

Higen FDA7002EX Specifications

General IconGeneral
BrandHigen
ModelFDA7002EX
CategoryServo Drives
LanguageEnglish

Related product manuals