F30 03  4 Start-up 
HI 800 473 E Rev. 1.00  Page 25 of 46 
4.1.1.1 Surges on Digital Inputs 
Due to the short cycle time of the HIMatrix systems, a surge pulse as described in 
EN 61000-4-5 can be read in to the digital inputs as a short-term high level. 
The following measures ensure proper operation in environments where surges may occur: 
1.  Install shielded input wires 
2.  Activate noise blanking: a signal must be present for at least two cycles before it is 
evaluated. 
i 
Activating noise blanking increases the response time of the HIMatrix system! 
 
i 
The measures specified above are not necessary if the plant design precludes surges from 
occurring within the system. 
In particular, the design must include protective measures with respect to overvoltage, 
lightning, earth grounding and plant wiring in accordance with the relevant standards and 
the instructions specified in the System Manual (HI 800 141 E or HI 800 191 E). 
 
 
 
4.1.2 Connecting the Digital Outputs 
Use the following terminals to connect the digital outputs: 
Terminal  Designation  Function 
1  L-  Ground channel group 
2  1  Digital output 1 
3  2  Digital output 2 
4  3  Digital output 3 
5  4  Digital output 4 (for increased load) 
6  L-  Ground channel group 
Terminal  Designation  Function 
7  L-  Ground channel group 
8  5  Digital output 5 
9  6  Digital output 6 
10  7  Digital output 7 
11  8  Digital output 8 (for increased load) 
12  L-  Ground channel group 
Table 17:  Terminal Assignment for the Digital Outputs