4 Start-up F30 03
Page 32 of 46 HI 800 473 E Rev. 1.00
4.3.4 Digital Inputs for F30
The following tables present the statuses and parameters for the input module (DI 20) in
the same order given in the SILworX Hardware Editor.
4.3.4.1 Tab: Module
The Module tab contains the following system parameters:
System parameter
Data
Type
R/W Description
DI No. of Pulse
Channel
USINT W Number of pulsed outputs (supply outputs)
Coding Description
0
No pulsed output planned for SC/OC
1)
detection
1
Pulsed output 1 planned for SC/OC
1)
detection
2
Pulsed output 1 and 2 planned for SC/OC
1)
detection
… …
8
Pulsed outputs 1...8 planned for SC/OC
1)
detection
DI Pulse Delay [µs] UINT W
Waiting time for line control (detection of short-circuits or
cross-circuits)
DI Pulse Slot UDINT W Pulse module slot (SC/OC
1)
detection), set the value to 3
DI.Error Code WORD R Error codes for all digital inputs
Coding Description
0x0001 Fault within the digital inputs
0x0002 FTT test of test pattern faulty
Module.Error Code WORD R Module error code
Coding Description
0x0000 I/O processing, if required with errors
see other error codes
0x0001 No I/O processing (CPU not in RUN)
0x0002 No I/O processing during the booting test
0x0004 Manufacturer interface operating
0x0010 No I/O processing: invalid configuration
0x0020 No I/O processing: fault rate exceeded
0x0040/
0x0080
No I/O processing: configured module not
plugged in
Module.SRS [UDINT] R Slot number (System Rack Slot)
Module.Type [UINT] R Type of module, target value: 0x00A5 [165
dec
]
1)
SC/OC (SC = short-circuit, OC = open-circuit)
Table 24: System Parameter for Digital Inputs, Module Tab